Installing an RV-92 |
[Down to Last] |
|
Post# 919574 , Reply# 1   2/5/2017 at 21:35 (2,635 days old) by combo52 (50 Year Repair Tech Beltsville,Md)   |   | |
Checkrate/Likes
 
     
Each two burner should be on its own 15 Amp 240 volt circuit breaker, 20 Amps if it has the Speed Burner for greatest safety, in most areas you can put them on one 30 Amp circuit and in some areas you can put a single wall oven on the same 40 or 50 Amp circuit, but you lose safety as you increase the Amp rating of the fuses or breakers. |