Post# 1015027   11/19/2018 at 13:15 (1,984 days old) by RP2813 (Sannazay)   |   | |
Checkrate/Likes
 
     
Our new place has a two year old Bryant series 915-S heating & air conditioning system. If you work in the HVAC field, you probably know what's coming next.
Now that the cooler weather has arrived, we're using the heat function for the first time, and it cuts out before reaching the desired set point on the thermostat, flashing the error code 33. Within a minute or so the system restarts. Lather rinse repeat.
I changed the filter, which was absolutely necessary since the previous owners had a dog and the existing filter was entirely covered in dog hair. That improved things only slightly. The literature from Bryant indicates a washable filter is recommended, but that's not what was in there. The replacement I used was a 3M Filtrete. Yesterday I bought a washable filter and replaced the 3M with it. Again, there's further slight improvement, but this morning it was 60 in the house so I set the thermostat to 68, and the system cut out at 64, then restarted and cut out a few more times before reaching the set temperature.
I went on line and googled error 33 and it appears to be an air flow issue (apparently the 3M Filtrete is the worst possible filter to use in this rig). Everything is blowing out fine through the registers in the house. One video on line has a guy cutting the sheet metal to provide an additional air intake into the side of the blower housing, stating that these Bryant furnaces all have a design flaw that allows it to get hot enough to trip a limit switch. Our model has a single speed blower, so there's no option to move the air any faster. I'm not going to cut into the blower housing, although doing so did resolve the guy's issue.
Is there any other way to fix this once and for all? I know it's a heat issue because we ran the A/C during the summer and it never cut out before meeting the set temperature.
Has there been any class action suit filed about this? It seems to have been a problem for several years. How does Bryant get away with selling something like this? How many perfectly good limit switches have been replaced on unnecessary service calls that ended up not resolving the issue?
Additionally, the heat function creates an odd odor. It doesn't smell like burning dust, which would have all burned off by now anyway. Instead and coincidentally, it smells similar to the smoke we're dealing with from the fire up north, but it was making this same smell before the fire started, and for the past week or so it hasn't stunk outside -- just really lousy visibility.
Thanks for any advice on this.
|
|
Post# 1015033 , Reply# 1   11/19/2018 at 14:02 (1,984 days old) by Yogitunes (New Jersey)   |   | |
Checkrate/Likes
 
     
I never had this error code....
the lower panel that allows access to the blower/motor---what would happen if you took that off and ran the heater?...still the same issue.....worst case you would have to buy a filter to go over the opening and duct tape that in place.... I used to do this trick to allow return air from the basement, since there were no return air vents down there, just registers only....it actually gave a better equalization of temps throughout the house.... I used 3M filters only during the winter, as for the Summer A/C use, it was too restrictive, and would freeze up the unit.... |
Post# 1015036 , Reply# 2   11/19/2018 at 14:09 (1,984 days old) by RP2813 (Sannazay)   |   | |
Checkrate/Likes
 
     
|
Post# 1015038 , Reply# 3   11/19/2018 at 14:15 (1,983 days old) by pulltostart (Mobile, AL)   |   | |
Checkrate/Likes
 
     
|
Post# 1015052 , Reply# 4   11/19/2018 at 16:23 (1,983 days old) by toploader55 (Massachusetts Sand Bar, Cape Cod)   |   | |
Checkrate/Likes
 
     
|
Post# 1015103 , Reply# 6   11/19/2018 at 23:19 (1,983 days old) by RP2813 (Sannazay)   |   | |
Checkrate/Likes
 
     
|
Post# 1015144 , Reply# 7   11/20/2018 at 06:54 (1,983 days old) by arbilab (Ft Worth TX (Ridglea))   |   | |
Checkrate/Likes
 
     
|
Post# 1015148 , Reply# 9   11/20/2018 at 07:51 (1,983 days old) by combo52 (50 Year Repair Tech Beltsville,Md)   |   | |
Checkrate/Likes
 
     
I think Johnathan [ reply #5 ] is on the right track.
This problem also sounded to me like an air flow problem.
Was the A/C coil replaced two years ago with the furnace ?, it could be clogged.
What is the BTU output of the new furnace ?, it could easily be too large for the duct-work.
What are the supply and return registers in the house like ?, many times they have been painted so many times that they restrict air-flow too much, or worse yet some one installed decorative wooden or even patterned metal ones that restrict air movement too much.
John L. |