Thread Number: 93081  /  Tag: Other Home Products or Autos
Ungrounded Outlets
[Down to Last]

automaticwasher.org's exclusive eBay Watch:
scroll >>> for more items --- [As an eBay Partner, eBay may compensate automaticwasher.org if you make a purchase using any link to eBay on this page]
Post# 1177080   4/4/2023 at 05:03 (386 days old) by chetlaham (United States)        

chetlaham's profile picture
I'm curious if anyone still has these in their home. How do you feel about them? Do you ever find them incompatible with a random plug? Do you have any pictures that you can share?


I personally have an embarrassing soft spot for the nostalgic look, however, that is no excuse to skip on safety. Its interesting to think though, if everything was double insulated these might still be around in many newer homes today.


  View Full Size



Post# 1177087 , Reply# 1   4/4/2023 at 08:57 (386 days old) by pulltostart (Mobile, AL)        

pulltostart's profile picture

Most of the houses that I've owned have been built about 1957, and typically do not have grounded branch circuits.  When I've painted and worked on the houses, I've always installed new 2-prong outlets in the old wiring.  In cases where newer wiring has been installed for additional circuits and they include a ground wire, I install the grounded outlets.  The current house was built in 1976 and all branch circuits are grounded, which is nice; however, there is a fair amount of aluminum wiring in the house so I have to be sure how the device is wired before I buy a new outlet or switch.

 

I have been told previously that it's illegal to replace an ungrounded device with a grounded one if the wiring doesn't include a ground wire.  This would probably be applicable when the house is sold and if the buyer is misled into thinking the house has 3-wire service throughout, only to find out later that that isn't the case.

 

lawrence


Post# 1177111 , Reply# 2   4/4/2023 at 11:39 (386 days old) by JoeEkaitis (Rialto, California, USA)        
Grew up in a house with 2-prongers.

joeekaitis's profile picture

 

The only grounded outlet was the 220V in the garage for the dryer.  The house was probably refitted to bring the outlets up to code after my parents passed away and we sold it.  It's a Levittown-inspired rancher (single story).

 

The house Cathy and I live in always had 3-prong outlets.  We added a 220V in the kitchen when we went from a gas stove to induction.  Both are in Rialto, CA.

 


Post# 1177114 , Reply# 3   4/4/2023 at 11:43 (386 days old) by qsd-dan (West)        
The only grounded outlet was the 220V

qsd-dan's profile picture

It was a 4 prong receptacle? I doubt that unless it was upgraded later on.

 

My grandparents lived in a house built in '63 that had 2 prong outlets. Never problem in the 40 years they lived there.


Post# 1177122 , Reply# 4   4/4/2023 at 11:58 (386 days old) by chetlaham (United States)        

chetlaham's profile picture
You can replace an ungrounded with receptacle with a grounding one provided that you protect the circuit with a GFCIs and install those stickers that come with the box saying "GFCI protected" / "no equipment ground".

Joe, I'm curious as well, was the receptacle three prong or four prong?


Some parts of the world like the Philippines still install ungrounded receptacles in residential.






Post# 1177124 , Reply# 5   4/4/2023 at 12:04 (386 days old) by Marky_mark (From Liverpool. Now living in Palm Springs and Dublin)        

marky_mark's profile picture

A 240-Volt electric dryer outlet in the US is always grounded, otherwise the dryer wouldn't work.  

 

They used to have a shared neutral-ground wire and used a 3-prong plug.  This wire is required, otherwise the motor, timer, lights etc., wouldn't work as they need 120 V.  The frame of the appliance is supposed to be connected to this neutral-ground wire.

 

Since about 1998 they have used a 4-prong plug with a separate neutral and ground.


Post# 1177135 , Reply# 6   4/4/2023 at 13:17 (386 days old) by qsd-dan (West)        

qsd-dan's profile picture

A 240-Volt electric dryer outlet in the US is always grounded, otherwise the dryer wouldn't work.  

 

 

In a 3 prong 240V design, everything is copasetic until a situation like a motor becomes "unbalanced" through use and more current flows through one hot prong than the other. The difference between the 2 flows through neutral becomes a live wire. Since both the neutral and ground wire are connected to the dryer cabinet, the surface of the dryer is now conducting electricity. It's a pretty rare occurrence but evidently happened enough in the past to mandate a 4 prong design in 1996.


Post# 1177136 , Reply# 7   4/4/2023 at 13:17 (386 days old) by cfz2882 (Belle Fourche,SD)        

My 1952 house has a few of those outlets still.Breaker box was upgraded in 1980 when some extra circuits were added.

Post# 1177139 , Reply# 8   4/4/2023 at 13:33 (386 days old) by chetlaham (United States)        

chetlaham's profile picture

A 240-Volt electric dryer outlet in the US is always grounded, otherwise the dryer wouldn't work.

 

 

Correct, the outlet has a grounded conductor but not a grounding conductor. Its a technicality which results in NEMA 10-30 and NEMA 10-50 receptacles being classified as "none grounding" types. 3 pole, 3 wire:

 

 

i.pinimg.com/originals/11/80/d5/...

 

 

https://www.ebay.com/itm/363342688746QUE...

 

 

Where as 6-30r and 6-50r are grounding types despite not having a neutral (2 pole 3wire).  Modern NEMA 14-30r and NEMA 14-50r with a neutral and ground (3 pole 4 wire) classified as grounding types.

 

Code makes a distinction between a grounding and grounded conductors even though in that past it was an inadvertently common

error to treat them interchangeably. Ie, you could ground a dryer through a neutral wire but you could not use the bare grounding wire in NM-B cable as the neutral.

 


Post# 1177143 , Reply# 9   4/4/2023 at 13:49 (386 days old) by chetlaham (United States)        
Neutral Becoming Live

chetlaham's profile picture

Yup! That was the big reason. Normally the the motor on a clothes dryer pulls roughly 5 amps.

 

 

10 gauge copper has a resistance of about 1.2 ohms per 1000 feet. So a reasonable worse case 100 foot home run would be 0.12 ohms. VD= IxR; would mean 5 amps  x 0.12 ohms = 0.6 volts on the frame of the dryer relative to other grounded objects like the cement floor or the washer. Typically 0.6 volts isn't even perceivable, so no harm in connecting the neutral to the frame.

 

That is until the neutral breaks, becomes loose underneath a screw, poor contacts in the receptacle, ect... then the frame of the dryers rises to 120 volts... One hand on the dryer, one on the washer, damp hands lowering skin resistivity... one does not have to imagine why the practice was deemed risky in modern times. 

 

 

For those over seas, here is the wiring diagram relevant to a US dryer-

 

3 wire:

 

 

i.stack.imgur.com/oYHa7.jpg...

 

 

4 wire:

 

i.stack.imgur.com/xB3g0.jpg...


Post# 1177145 , Reply# 10   4/4/2023 at 14:26 (386 days old) by Marky_mark (From Liverpool. Now living in Palm Springs and Dublin)        

marky_mark's profile picture

True.  I knew I wasn't being very accurate when I said the wire was a combined neutral-ground, as it is technically a neutral wire (grounded conductor) that is also used to ground the dryer's frame.  

 

I think the reason it was changed is that just one single fault could cause the dryer's frame to become live, therefore able to deliver a fatal electric shock.  This would happen if the neutral wire broke at some point along the circuit. 

 

With the 4-prong design, I think you would need two simultaneous faults to cause this, i.e. first a break in the ground wire AND then another fault causing the live wire to contact the frame.

 

As for the ungrounded two-prong outlets of yesteryear, I think I may have seen these once or twice in older mid-century homes in Palm Springs, but even then it's only been the odd one or two.  I have certainly seen them for sale at Home Depot.  Yes they are kind of cool, if they are original to the house.  I like that!


Post# 1177152 , Reply# 11   4/4/2023 at 15:43 (386 days old) by chetlaham (United States)        
Technically you would be correct in the UK

chetlaham's profile picture

To be fair, Under IEC / BS7671 standards the neutral conductor in the same Edison circuit if replicated outside the US would be classified as a PEN conductor, Protective Earth Neutral, and thus you would be correct in calling it a combined neutral-ground.

 

The NEC however requires it be treated it as a grounded conductor, that only by special exceptions given in the code, can ground the frame of the range or dryer.

 

In Eastern Europe it was common to have TN-C up to the sockets. You would only have two wires, Live and PEN, and the PEN conductor would land on the earth terminal and then jumper to the neutral terminal. Today this is forbidden, a hold over practice from the days of the soviet union.

 

 

www.asutpp.com/tn-c-earth...

 

 

You are correct, you'd need at least 2 failures, and with the recent code changes you'd need 3 failures. Code now requires most US dryers to be GFCI protected. The idea is that if you lost the equipment grounding conductor with a simultaneous insulation break down the GFCI would act as a last resort and trip.

 

 

www.electricallicenserene...

 

 

I think, that as time goes on all circuits in the US will require some form GFCI or GFP protection regardless of voltage, wiring method, rating, or equipment installed. Equipment grounding conductors can and do become compromised in a world where newer standards of safety dictate that multiple things must go wrong first before any danger becomes present. 


Post# 1177164 , Reply# 12   4/4/2023 at 17:13 (386 days old) by SudsMaster (SF Bay Area, California)        

sudsmaster's profile picture

I guess I am lucky here because this 1941 house was remodeled sometime in the 1960's or 70's. At that time one of the bedrooms (2) was converted to a family room, with a washer dryer closet,  and another bedroom was added to the rear of the home, with its own bath. All the 120 outlets in the main house and other structures are three prong, grounded.

 

However, perhaps this was all done before four prong 240 volt plugs became the standard, because the plug for the original 240 volt dryer (which I soon replaced with a gas version), and all the rest of the 240 volt plugs, such as in the separate workshop (1,000  + sq ft) are all three prong. Never had a problem with any of those. I have seen four prong outlets and plugs at places like Home Depot, and always wondered what if anything they added. Now I know, so thanks.


Post# 1177170 , Reply# 13   4/4/2023 at 18:21 (386 days old) by CircleW (NE Cincinnati OH area)        

My house was built in 1952, and all original 120 volt receptacles were 2 prong. As the years went on, a few new circuits were added, with the 3 prong grounding type installed. When I started the renovation, I removed all the existing wiring except for an abandoned circuit in the one room where I didn't remove the wall surface. Therefore, I have one 2 prong receptacle left in the house, though not in service. I plan to do some work in there, and it will be replaced with a new receptacle and cable.

As to 240 volt 4 wire receptacles for ranges and dryers, this is required because some parts of those appliances operate at 120 volts. That would be lights on a range, and older models used 120 for low heat settings. Dryer motors operate at 120 volts. If the appliance operates solely on 240 volts, such as an air conditioner or heater, the cord and plug are only 3 wire.

While the code started requiring 4 wire circuits for all new 120/240 installations in the 90's, it was required many years earlier in certain circumstances. One of these was in mobile homes, and another was any 120/240 volt circuit originating in a panelboard OTHER than the MAIN SERVICE ENTRANCE. The high school I attended, which was built in 1966, had 4 prong receptacles for all the ranges and dryers in the home-ec room. Other places they were found was in commercial buildings and large homes that had numerous panelboards throughout the building.



Post# 1177199 , Reply# 14   4/4/2023 at 23:08 (385 days old) by fan-of-fans (Florida)        

They are kind of neat to see. That said, I would probably avoid buying a home with ungrounded wiring since a lot of appliances these days have grounded cords, not just things like washers and refrigerators.

And surge protectors won’t work properly without a ground.

On a side note, I don’t like how replacement 2 prong outlets from both Eaton and Leviton don’t have the slots centered in the circles anymore. These days they look like a 3 prong that’s had the ground hole filled in, the slots are offset and it looks silly.


Post# 1177202 , Reply# 15   4/5/2023 at 01:16 (385 days old) by CircleW (NE Cincinnati OH area)        

Another thing is that all 2 prong receptacles sold today that I'm aware of are the cheap residential grade. I've not seen any specification or commercial grade receptacles that aren't the grounding type in many years. Residential grade devices have no place in a premium grade wiring system.

Post# 1177214 , Reply# 16   4/5/2023 at 06:19 (385 days old) by chetlaham (United States)        

chetlaham's profile picture

I know what you mean about the replacements. Leviton and Eaton are no longer centered and I'm not sure about the others. Really makes me upset. Do you know about the other brands?


Post# 1177218 , Reply# 17   4/5/2023 at 08:27 (385 days old) by DaveAMKrayoGuy (Oak Park, MI)        

daveamkrayoguy's profile picture
The house I grew up in has had and still has to this day, ungrounded two-prong outlets which supposedly a three prong adapter could safely ground, in use of heavy duty appliances such as refrigerators and washers as well as supposrting electrical implements on gas dryers and gas stoves...

So far I haven't seen one outlet become replaced by anything three prong, except in the house I live in now having been built years later has three prongs, all grounded, but maybe meaning that the side of town I live in just conforms to updating to modern standards, versus my o.d neighborhood not being such except in the case of renouvations a number of homes with exception of that last remnant of being upgraded and updated to...

Lastly, in terms of safety, we'd never encountered anything where such renewal was ever mandated due to any unsafe electrical mishaps--there weren't ever any...



-- Dave


Post# 1177241 , Reply# 18   4/5/2023 at 18:10 (385 days old) by chetlaham (United States)        

chetlaham's profile picture

Code only requires upgrades if a device is replaced, or more commonly if the wiring is being extended/upgraded to a significant degree. The rest is considered grandfathered, so, it can legally remain for the rest of eternity. Fuse panels and knob and tube are nowhere near as bad as people make them out to be, provided they've not been illegally tampered with.

 

 

In some ways it would be kind of cool if everything in homes were double insulated- no way anything could ever become live. Two wires at the service head, 2 pole breakers, 230 volt appliances.  Here is such a main panel being made up in the Philippines: 

 

 

 




 

 

Like Japan they us two wire romex through out the home, and 3 wire romex for the 3 way switching. I think blue and yellow would make good vibrant contrasting colors here in the states- with blue, yellow and red for the 3 wire romex.

 

 

 

 

 

 

 


  View Full Size
Post# 1177246 , Reply# 19   4/5/2023 at 20:09 (385 days old) by bradfordwhite (central U.S.)        

bradfordwhite's profile picture
I especially like them in a baseboard and original not painted like in this photo

  View Full Size
Post# 1177294 , Reply# 20   4/5/2023 at 23:59 (384 days old) by qsd-dan (West)        

qsd-dan's profile picture

Some of those old sockets are only rates for 10 amps, gotta be carful plugging high amp draw appliances in them.


Post# 1177301 , Reply# 21   4/6/2023 at 05:57 (384 days old) by chetlaham (United States)        

chetlaham's profile picture

I think its 10 amps at 240 volts, 15 amps at 120 volts. This was the pre-NEMA days and the code at the time had a silly rule that some devices had to be rated less amps at higher voltages. 

 

I wish the US had settled on 240 volts instead of 120. We'd probably have 10 amp general use circuits wired in 16 AWG copper.

 

I love your pic btw! :)


Post# 1177321 , Reply# 22   4/6/2023 at 13:21 (384 days old) by Davey7 (Chicago)        

My late 20's apartment had grounded receptacles, even though they were two prong thanks to Chicago being a conduit town. Only place they weren't grounded was some handyman added receptacles from circa 1960. I replaced all the paint caked receptacle when I moved in with grounded except on those circuits (and the high voltage ac circuits). I always laugh at the receptacle where I grew up - we'd always been told the outlet for the fridge was in conduit and the adjacent receptacle was tapped off that one. Nope, when the kitchen was redone, we discovered it was the other way and the fridge was powered off two random wires behind a baseboard...

Post# 1177343 , Reply# 23   4/6/2023 at 18:26 (384 days old) by WhiteWhiskers (Silicon Valley, California)        
re: Reply# 16

whitewhiskers's profile picture
Amazon is selling a centered ungrounded outlet in ivory color for $6.49, ships and sold by Amazon:
www.amazon.com/Leviton-22...

or you can buy a 10-pack in white for $20.98. Sold by a third-party but ships from Amazon:
www.amazon.com/Leviton-Du...

It's good to remember "the wide slot is white", meaning the neutral is the wide slot, connected to the white wire, which is the neutral, and the outlet is installed with the wide slot on the left side. The ivory outlet as pictured on Amazon is correct but the white outlet is upside down.

Also, if you're going to do any electrical work, buy WIRING SIMPLIFIED. It's the greatest and only book you will ever need.


CLICK HERE TO GO TO WhiteWhiskers's LINK


  Photos...       <              >      Photo 1 of 3         View Full Size
Post# 1177352 , Reply# 24   4/6/2023 at 20:12 (384 days old) by SudsMaster (SF Bay Area, California)        

sudsmaster's profile picture

Looks like a good book.

 

Just ordered a copy.

 

 


Post# 1177358 , Reply# 25   4/6/2023 at 20:44 (383 days old) by chetlaham (United States)        

chetlaham's profile picture

If feeling nostalgic,  here is the 1956 version of Wiring Simplified:

 

 

inspectapedia.com/electric/Wirin...

 

 

 


Post# 1177371 , Reply# 26   4/6/2023 at 21:36 (383 days old) by SudsMaster (SF Bay Area, California)        

sudsmaster's profile picture

Well, that's a big outdated, no?

 

In any case, I placed the order, but still waiting for word from the store that the order is ready to be picked up. I suspect it won't be ready until Friday morning. We'll see!

 


Post# 1177373 , Reply# 27   4/6/2023 at 21:52 (383 days old) by chetlaham (United States)        

chetlaham's profile picture

Outdated bigly. As in most of the 1956 version is no longer code compliant. Still fun to read though. smile


Post# 1177382 , Reply# 28   4/6/2023 at 22:37 (383 days old) by kenmore70 (New York)        

What kind of appliance would require an outlet like this, with the horizontal slot? I thought I read some type of air conditioner plugs require an outlet like this but I have never seen them.

  View Full Size
Post# 1177383 , Reply# 29   4/6/2023 at 23:19 (383 days old) by qsd-dan (West)        

qsd-dan's profile picture

 

What kind of appliance would require an outlet like this, with the horizontal slot?

 

20 amp socket

 

Sometimes used with high-power microwave ovens, heaters, large old A/C window units, and large power tools.


Post# 1177384 , Reply# 30   4/6/2023 at 23:24 (383 days old) by CircleW (NE Cincinnati OH area)        

The receptacle pictured above (reply #28) is a 20 amp 120 volt device (NEMA 5-20). These are installed mainly in kitchens and laundry rooms, as a few appliances have plugs that require these. Also seen in workshops and garages, as some tools require them. Most commonly used in commercial buildings.

Post# 1177391 , Reply# 31   4/7/2023 at 01:07 (383 days old) by Adam-aussie-vac (Canberra ACT)        
My question is

In regards to the Nema 620, if someone were to import compliance from a 220 V single phase country and connected to the 220 V split phase found in the USA, would that appliance work happily with that? excluding the usual suspects like motor powered clocks and microwaves or things that use the AC frequency for time

Post# 1177405 , Reply# 32   4/7/2023 at 06:30 (383 days old) by WhiteWhiskers (Silicon Valley, California)        
re: reply# 24

whitewhiskers's profile picture
Chetlaham, thank you for posting the link to the 1956 Wiring Simplified. My copy is the 39th edition from 1999, purchased in the electrical department of Home Depot. Even though a lot has changed from 1956, some things stay the same. Notice how the 1956 receptacle diagram uses ungrounded outlets while the 1999 diagram has the ground hole. The ground wire isn't shown though.

  Photos...       <              >      Photo 1 of 2         View Full Size
Post# 1177410 , Reply# 33   4/7/2023 at 09:30 (383 days old) by chetlaham (United States)        
Working Happily

chetlaham's profile picture

Much indeed. As long as said appliance can handle 60Hz, which most can, even if listed for only 50Hz, can't tell the difference. Schuko plugs aren't even polarised so the fact any leg could/is live is taken into account safety wise.

 

 

I do this in my own home. I refuse 120 volts when I can avoid using it. I find the added engineering effort of bootlegging an impractical half voltage out of a system so odd/dated/absurd/risky. Extra effort and material just stepping backwards.

 

 

 

 

 

 


  Photos...       <              >      Photo 1 of 4         View Full Size
Post# 1177411 , Reply# 34   4/7/2023 at 09:54 (383 days old) by chetlaham (United States)        

chetlaham's profile picture

Being honest even the new additions of the book come across as dated, but, at the same time, as long as the graphics are revised to follow the lasted addition of NFPA-70 it suites its job well in teaching people. 

 

 

There is one important thing that I want to clarify about that book and most other wiring books. When they use the term"ground" "going to ground" "traveling to the ground" or "grounded" in relation to clearing a fault they are referring to the path electricity takes back to the utility transformer and not the earth or soil itself. Very common misunderstanding. A typical ground rod comes in at 25 ohms and will not trip a breaker, where as a typical service neutral rarely exceeds 0.1 ohms. Fault current travels back to the main panel (or disconnect) via metal conduit or grounding conductors, to the grounding terminal in the enclosure, through the main bonding jumper, to the neutral bar and up through the service neutral going back to the transformer. It is one closed loop. The soil, earth or terra firma makes no difference in that regard.     

 

 

 smile

 

 

 


  View Full Size
Post# 1177535 , Reply# 35   4/8/2023 at 09:20 (382 days old) by polkanut (Wausau, WI )        

polkanut's profile picture

Our house is a mixture of grounded & ungrounded. The original part of our house was built in 1925, and the addition was built around 1962. Funny thing though, the man who owned the house before us was in the electric motor repair business for over 50 years. You would've thought that he would have updated the electrical over the years, but this was not the case. In fact, we upgraded to a 100-amp service with a breaker box vs the old 60-amp service with only 4 fuses for the entire house.


Post# 1177552 , Reply# 36   4/8/2023 at 12:26 (382 days old) by Adam-aussie-vac (Canberra ACT)        
Reply 33, I would absolutely love to see a thread on 220 V

Appliances and how you got your system to work
Plus I do hope you have a 220 V coffee maker, if you don’t I can happily supply one


Post# 1177567 , Reply# 37   4/8/2023 at 13:57 (382 days old) by fan-of-fans (Florida)        
Re ungrounded with centered slots on Amazon

That is interesting. I do know at Home Depot the outlet on the display has the slots centered, but if you look at the ones for sale in the bin, they aren’t centered.

As for other brands, I believe Pass and Seymour/Legrand may still sell ungrounded ones with centered slots. But since Lowes switched to Cooper/Eaton here, nobody seems to sell P&S around here, so I cannot confirm.

The horizontal blade 20 amp plugs are also used on some small commercial cooking equipment that requires a 20 amp circuit. I can’t think of anything that I’ve seen sold toward residential use that does though.

The 20 amp outlets are usually seen in kitchens and baths of houses around here built in 80s and later, although even n the grandmothers 1978 home had them in the kitchen. I don’t know that there’s any code that says they have to be used specifically.


Post# 1177617 , Reply# 38   4/8/2023 at 21:27 (381 days old) by gizmo (Victoria, Australia)        

That 5-20R with 1 horizontal, one vertical slot is interesting. Do they always have a ground pin?

Without the ground pin it looks the same as our ELV (Extra Low Voltage) plug and socket in Australia, used for low voltage DC wiring - they are 2-pin only, one horizontal and one vertical pin.

 

They are somewhat unusual these days, used to be for 32V DC remote area homes with a 32 volt DC home battery system, powered by a wind generator and/or a diesel powered home lighting plant. You could buy vacuum cleaners, washing machines, irons and lights that ran on 32V DC with these plugs. They have come back into use in the solar era, mostly for 12V DC, now sometimes used in RVs for a more reliable connection than a 12 volt cigarette lighter plug.

 

I have them in my home, our place is wired dual-voltage, standard Australian 240V AC power outlets throughout the home and 12V DC outlets in a couple of strategic places only - mainly to run small devices direct from the DC batteries without the inverter. They don't get used much, our usage has changed. Our battery system is 24V DC and there is a DC:DC converter to provide 12V from the 24V batteries.

 

Could be spectacular if someone plugged an Australian 12V or 32V DC appliance into a US 120V 20A AC socket...

 


  Photos...       <              >      Photo 1 of 2         View Full Size
Post# 1177621 , Reply# 39   4/8/2023 at 22:03 (381 days old) by fan-of-fans (Florida)        
Horizontal slot with ground?

My guess is yes, likely they would always have a ground prong. All the plugs I’ve seen with them did. Just being that most of that type of equipment is made of metal and possibly used in wet environments. And most items with those 20 amp plugs I’d guess would be made in the era that grounding was common.

Now what interests me also, are those old receptacles with both slots being T slots. From my understanding there were some early 15 amp plugs made that had two horizontal slots instead of the parallel ones. But I can’t ever encounter finding one of these.

Also, I have some older receptacles in my collection, including a crows foot receptacle that was used for early grounded appliances prior to the 1950s!

The crows foot slot pattern looks similar to the ones to the right of your picture.


Post# 1177670 , Reply# 40   4/9/2023 at 08:18 (381 days old) by gizmo (Victoria, Australia)        
right side of my picture

Right side of my picture is a regular 240 V 10 A Australian power outlet (we call them "power points.") They are required to be individually switched here. 240V x 10 A = 2400W max. per socket.

 

I remember seeing them, or something that looked like them, in a hospital in Chicago in 1982 - but unswitched. I guess they were used for some 240V medical equipment?


Post# 1177673 , Reply# 41   4/9/2023 at 08:56 (381 days old) by DADoES (TX, U.S. of A.)        

dadoes's profile picture
 
A piece of network equipment at the Internet service where I worked required 120v 20a.  The APC UPS unit for it had an optional backplane with two of the required receptacles.


Post# 1177674 , Reply# 42   4/9/2023 at 08:57 (381 days old) by Adam-aussie-vac (Canberra ACT)        
Oh, you’re probably thinking about the 6–10 Nema

It’s electrically compatible with Australian stuff but that plug-in outlets up are rated for 15 A at 120 and 10 at 240

Post# 1177714 , Reply# 43   4/9/2023 at 20:00 (381 days old) by chetlaham (United States)        
Chinese Version

chetlaham's profile picture

I have a few of these. This was one of several socket types I experimented with until I settled with schukos. Some models have a socket switch others do not. Some come with a parallel combo NEMA 1-15 / Euro plug.

 

 

 


  Photos...       <              >      Photo 1 of 3         View Full Size
Post# 1177716 , Reply# 44   4/9/2023 at 20:05 (381 days old) by chetlaham (United States)        
Old US non NEMA Version

chetlaham's profile picture

I personally wish this was the dominant outlet in the US for many reasons, and it was supposed to be so, unfortunately someone must've traveled back in time screwing with critical events resulting in the after-thought NEMA 1-15/NEMA 5-15 we are stuck with today.


  Photos...       <              >      Photo 1 of 4         View Full Size
Post# 1177719 , Reply# 45   4/9/2023 at 20:07 (381 days old) by chetlaham (United States)        
Australian Adapter

chetlaham's profile picture

The modern AUS adapter fits perfectly in Chinese and old non NEMA US versions- 


  Photos...       <              >      Photo 1 of 6         View Full Size
Post# 1177720 , Reply# 46   4/9/2023 at 20:12 (381 days old) by chetlaham (United States)        
NEMA 10-50

chetlaham's profile picture

This is a NEMA 10-50 range receptacle rated 50 amps and considered "ungrounded" in NEMA standards .

 

I personally wish the NEMA 10-20, 10-30 and 10-50 were re-classified as grounding types (as has been done in some parts of the world) plus reintroduction of the old US crow foot.


  Photos...       <              >      Photo 1 of 3         View Full Size
Post# 1177721 , Reply# 47   4/9/2023 at 20:24 (381 days old) by chetlaham (United States)        
Chinese Getting It Right

chetlaham's profile picture

The Chinese are building these as grounding versions (technically incorrect by US standards) where the neutral pole is the grounding pole with a bonding strap to the yoke of the receptacle, pole Y as the hot and pole X is the second live or neutral when used in a 230/400Y system. cool

 

Very smart, and common sense. The round ground pins on other NEMA and NEMA-esque receptacles are essentially after thoughts, and do not make surface gripping contact the way flat contacts do.

 

https://www.amazon.com/Sintron-Straight-Receptacle-Suitability-Industrial/dp/B08HSYF96M/ref=sr_1_27?crid=L1XFT6TPREM2&keywords=nema%2B10-50&qid=1681089053&sprefix=nema%2B10-50%2Caps%2C119&sr=8-27&th=1


  View Full Size
Post# 1177722 , Reply# 48   4/9/2023 at 20:33 (381 days old) by Adam-aussie-vac (Canberra ACT)        
Reply 44

Oh wow I would love to get my hands on one of those outlets, speaking Of outlets, there’s also this one as well which I actually use on a daily basis, And yes it actually does fit USATwo gang electrical boxes, and it even has those little tabs that you can break off to separate an outlet into to outlets

Prepare to be amazed or horrified

Oh yeah the second photo is the cord that I use on the Two prong outlet with the Center screw as ground


  Photos...       <              >      Photo 1 of 2         View Full Size
Post# 1177724 , Reply# 49   4/9/2023 at 21:00 (380 days old) by chetlaham (United States)        

chetlaham's profile picture

Amazon is the key. Try the US version, among others, that have on/off popups with Chinese sellers. Ebay for the old stuff.

 

 

In Japan they'll do that, where the cord has a separate ground wire and separate ground screw on the socket. Not something I approve of, but common there it seems.


  View Full Size
Post# 1177725 , Reply# 50   4/9/2023 at 21:01 (380 days old) by chetlaham (United States)        
2 Prong Combo Light Socket

chetlaham's profile picture

This I came across on Amazon at a reduced price. When I saw it I had to get it.  


  View Full Size
Post# 1177819 , Reply# 51   4/10/2023 at 20:13 (380 days old) by SudsMaster (SF Bay Area, California)        

sudsmaster's profile picture

Technically speaking, the 10-50 and similar 240 volt receptacles are NOT fully grounded. This has been explained elsewhere in this thread (I think). For the safest ground, a separate path for the ground is needed; the 10-50 and similar outlets compromise this with the neutral wire. It's no safer (and perhaps less safe) than a 120 volt outlet with just two paths. One for hot, the other for neutral/ground.

 

That said, my laundry area in the main house, as well as the 240 volt outlets in the workshop, have only three prong outlets. Since I rarely use any of these (the dryer is gas), I'm in no hurry to change them to the latest and safest version. Some day!

 

Oh wait... there is a 240 volt air compressor in the workshop that I use whenever I need to fill tires. It also has a 3 prong plug. Oh well.


Post# 1177822 , Reply# 52   4/10/2023 at 21:03 (379 days old) by chetlaham (United States)        
Correct

chetlaham's profile picture

Under NEMA they are classified as non grounding H-N-H.

 

 

However, my line of thinking is have everything go straight 240 volts. No internal 120 volt components. Have everything be 3 wire, H-G-H, and just reclassify the 10-XXs and 18-XXs as grounding types. Have the crow foot become dominant. Ditch all the other NEMA types.

 

At least in my world...


Post# 1177824 , Reply# 53   4/10/2023 at 21:31 (379 days old) by chetlaham (United States)        
Reply 36

chetlaham's profile picture

The US residential system is split phase, a center tapped 240 volt winding. Each home receives two hots and one grounded neutral. The system is TN-C-S or rather technically PME.  Both hot legs are 180* out of phase, so between each hot and neutral (of ground) we get 120 volts, but between each hot wire we get full 240 volts. 

 

 

en.wikipedia.org/wiki/Split-phas...


  Photos...       <              >      Photo 1 of 3         View Full Size
Post# 1177831 , Reply# 54   4/11/2023 at 00:38 (379 days old) by CircleW (NE Cincinnati OH area)        

There are already grounded receptacles for equipment that operates solely at 240 volts. For example, the NEMA 6-50 is rated for 50 amps, no neutral - just the equipment ground. That said, I've seen installations that used the 10-50 for that purpose.

Post# 1177838 , Reply# 55   4/11/2023 at 05:56 (379 days old) by ozzie908 (Lincoln UK)        
UK outlets

ozzie908's profile picture
May leave some people agog but they are all switched and all earthed/grounded even light fittings are grounded.

No matter what you choose to connect there is no extra wiring needed apart from Stove's and showers.

All plugs are three prong too and each plug is fused for safety they may be bulky but it makes life safer and easier


Post# 1177853 , Reply# 56   4/11/2023 at 11:33 (379 days old) by chetlaham (United States)        
Reply 54

chetlaham's profile picture

I know smile

 

I'm saying ditch all 120 volt components and just reclassify the NEMA 10 and 18 as grounding types. Fewer receptacles moving forward.

 

Regarding the UK, I think they have on of the best systems in the world.


Post# 1177855 , Reply# 57   4/11/2023 at 12:13 (379 days old) by donprohel (I live in Munich - Germany, but I am Italian)        
UK plugs

I am not at all sure that the fuse make UK plugs much safer: the fuse in the plug is required because of the very peculiar way electric circuits are made in the UK, and the fuse is there to protect the wirings in the wall.

I feel much, much, much safer with the Residual Current Devices I have now than with fused plugs.

And it is true that all the plugs have three pins, but that does not mean that any device is grounded: sometimes the ground plug is just plastic and the device is not grounded at all (for instance, plug-in power supplies are not grounded)


Post# 1177858 , Reply# 58   4/11/2023 at 12:48 (379 days old) by chetlaham (United States)        

chetlaham's profile picture

The wiring in the wall is already protected via MCB. The fuse protects to cord itself and also reduces the amount incident energy released at the point of short circuit, if the cord became shorted. With a 32 amp MCB the cord may melt before the MCB trips (adiabatic limit of the cord's conductor exceeded), or just arc/sputter at the point the cord is damaged, but with the fuse (in the plug) a fault in the cord instantly blows said plug fuse before anything bad can happen. The fuse responds faster, at a lower current, than the 32 amp MCB can. 

 

 

Ring circuits, at least back in the day, allowed much more power to be supplied to a building level via less copper. The load diversity also helped maximize the savings as it is not likely everything would be on at once. A whole residential lower level could be fed from a single 32 amp circuit, a second 32 amp ring socket  circuit for the upstairs, then one or two 6 or 10 amp radial lighting circuits. A 40 amp for the cooker, maybe another circuit for the boiler. 

 

 

There has to be a ground pin on the plug even if the appliance is double insulated as the safety shutters in the plug will not open. Ingenious idea as the shutters provide both child protection and rejection of a plug missing its ground pin. In the US missing equipment ground pins on metal tools like drills made for the bulk of electrocutions. 

 

 

 Attached Image courtesy of "Fatally Flawed"

 

 

 electrical.theiet.org/wiring-mat...


  View Full Size
Post# 1177893 , Reply# 59   4/11/2023 at 19:50 (379 days old) by CircleW (NE Cincinnati OH area)        
"whole residential lower level"

Placing everything on any particular floor level or major area of a building on one circuit is very poor design. In the event the circuit breaker trips or fuse blows, that entire area is left in the dark. Some friends moved into an old house wired like that, and a fuse blew leaving the entire first floor dark except the bathroom. The 2nd floor was also on one circuit. They soon had the house totally rewired. Also, kitchen appliance circuits should never serve any other rooms except a dining room or pantry.


Post# 1177900 , Reply# 60   4/11/2023 at 22:24 (378 days old) by chetlaham (United States)        

chetlaham's profile picture

UK homes typically have at least one 6 or 10 amp radial lighting circuit in that should the ring MCB blow, hardwired ceiling and wall mounted fixtures are still functional.

 

A 32 amp ring and one 10 amp lighting circuit in the UK can supply more power than 4 120 volt circuits- two rated at 20 amps and two at 15 amps in a typical US home. Hence there are no code requirements restricting a circuit to any particular area as you find in the NEC. 


Post# 1178066 , Reply# 61   4/13/2023 at 23:27 (376 days old) by SudsMaster (SF Bay Area, California)        

sudsmaster's profile picture

Well, went to Home Depot and picked up my copy of  "Wiring Simplified". It looks good.

 

If I have a complaint, though, it would be that the type is a bit small. Not so small that I need a magnifier, but sort of on the edge.

 

Anyway, I'm wondering if the original edition was in a larger format (2017 version or earlier, that is). Maybe not, since the added size might adversely affect sticking it in a tool box. LOL.

 

Anyway, I'll be roaming through Wiring Simplified over the next few days/weeks/months.

 

PS- About 40 years ago, I had a temp job with an electrical contractor who had helped wire a new building for the lab I was working. Wiring Simplified would have been a good read back then, too.


Post# 1178177 , Reply# 62   4/15/2023 at 07:46 (375 days old) by combo52 (50 Year Repair Tech Beltsville,Md)        
Reply number 47, Chinese getting it right?

combo52's profile picture
I’ve never seen a receptacle in the US where the metal mounting bracket is not connected to either the ground or the neutral, depending on the outlet configuration, etc.

John



Post# 1178233 , Reply# 63   4/15/2023 at 15:38 (375 days old) by chetlaham (United States)        

chetlaham's profile picture

Have a look at the pictures in reply #46.

 

 

There is no strap between the neutral terminal and the receptacles yoke.

 

This is correct for a listed NEMA 10-30r and 10-50r.

 

 

I encourage you to look at any NEMA 10-30 or 10-50 made by a reputable brand like Leviton, Hubbell, Eaton, Legrand, ect.


Post# 1180186 , Reply# 64   5/9/2023 at 07:44 (351 days old) by chetlaham (United States)        
Got Some For the Collection

chetlaham's profile picture

the white ones were sold out, but I did manage to get some brown ones-


  Photos...       <              >      Photo 1 of 4         View Full Size
Post# 1180201 , Reply# 65   5/9/2023 at 12:40 (351 days old) by bradfordwhite (central U.S.)        

bradfordwhite's profile picture
According to the book, in 1956 one could still freely install knob and tube wiring but it also says most people don't because it's too expensive. lol

These days the ideal electric system would have all lighting wired as 12 volt DC, most outlets in the bedrooms, living rooms, and offices/libraries being 12 volt DC with USB outlets.

Really the only place 120 volt AC is needed is at specific appliances like the water heater, washing machine, kitchen counter, etc. and most of those appliances are located in only a few rooms.

With the main wiring system being 12 DC it's easy to draw power from a solar system battery bank. All the LED lights are low voltage and need to have built in transformers to work on the current 120volt AC set up.

I think I would put one 120 v AC outlet in each bedroom or living room next to the entrance at a convenient height of 30"


  View Full Size
Post# 1180257 , Reply# 66   5/10/2023 at 08:48 (350 days old) by gizmo (Victoria, Australia)        
12V DC wiring...

I have a dual-voltage wired home - 12 V DC and 230 V AC.

There are disadvantages to 12 V too - voltage drop over distance becomes much more significant, you need short wire runs and heavy cables to keep voltage drop to a minimum. The cables are substantially more expensive than regular household cable for 240V.

Most "real" solar power systems (ones really designed to run a home, not just tinkering with the concept) have higher battery voltage than 12V - most these days are 48V DC, some are higher than that. So if you want 12V DC outlets, you need a DC:DC converter.

 

My battery voltage is 24V, that was common when we built this house but as systems have become larger, 48V is the standard now. We have a DC:DC converter to provide 12V from the 24V battery bank, it is limited to 10 amps at 12 volts. (You can get bigger ones.)

The only thing we still use on the 12V side is a couple of lights in the kitchen. In the early days we also ran TV antenna booster; cordless phone base station; and a small fan to circulate air from our wood heater, but all these gadgets are either no longer used, or replaced with something that doesn't use 12V.

 

The original thinking was that we have a quite sophisticated  Australian-made inverter that goes into a power saving mode when there is no load on it, cutting battery power consumption to just a couple of watts. Once every second it checks for a load and if it finds a load (minimum is about 3 watts) then it turns on, which draws about 15 watts minimum to run the inverter for even the smallest load. If the load falls below 3 watts, the inverter turns off and goes back to standby mode. This works really well, better than most new inverters today, which are more "made to a price" than ours. The thing is, we have a much bigger solar array - originally we had 1.2 kW of panels at this house, then upgraded to 2.4, then 3.6 and we are about to increase it to 4 kW. (Which is the most we can fit on the garage roof.) We have some gadgets that must be powered 24/7 such as mobile phone signal booster and printers, as well as phone chargers we use at night, so the inverter is now on 24/7 and hasn't dropped back to standby mode for years. We now have enough panels to cover this background power consumption. So we don't really need the 12V DC wiring, I'm not sure if I'd bother if we had to build this house again. (heaven forbid!) I might still have some DC lights, so that in case the inverter fails we would still have lights.

One thing I might do in future is install some USB outlets on the 12V DC circuit. You can't have too many these days. I'll look into that, I'm not sure how easy it is to find USB wall outlets that take a 12V DC  supply.

 

As a funny aside, we laid some very heavy DC cables from the battery shed to the house to give us the option to run a special low voltage 24 V DC fridge. These cables are huge as the low voltage DC fridge compressors at the time were very sensitive to voltage drop. The converted fridges cost over $2000 so we didn't get one at the beginning, we used an LPG fridge. Then we added more solar panels, and standard fridges got way more efficient, so we just got an efficient 240V AC fridge. The expensive DC cables we laid 20 years ago have never been used. They are still there...

 

We also wanted to be all future-proof, so we put cat 5 data-grade phone cables to most rooms, so we could have dial-up internet in each of 5 rooms... We no longer have a land line phone connection at all, the whole system, including 250 metres of cable from the front gate to our house, is redundant. It took me two whole days with a hired trenching machine to dig the trench for that cable... D'oh!


Post# 1180271 , Reply# 67   5/10/2023 at 12:07 (350 days old) by chetlaham (United States)        

chetlaham's profile picture

I like space space heaters though. 120/230 has its place.


Post# 1180385 , Reply# 68   5/11/2023 at 21:26 (348 days old) by bradfordwhite (central U.S.)        
#66

bradfordwhite's profile picture
Yes with D.C. one has to be cognizant of voltage drop even from room to room but it's mainly within one's home. Most solar arrays are on the roof or near by. Having to beef up some branch main lines is a small price to pay for energy independence imo.

I suggest the 12 volt for simplicity sake. Avoiding transformers and the like which can be high maintenance, expensive to replace and points of noise, heat, and energy usage. I'd rather invest money one time in thicker gauge wires so one can move power from one point in a home to another efficiently. Copper wires don't break down.

An independent 48 volt system is preferred for the few high watt use appliances where stepping up the 12 volt to 120 volt AC is preferred.

Technology is always changing, becoming more affordable and easier to use. It's just incredible.


Post# 1180449 , Reply# 69   5/12/2023 at 17:35 (348 days old) by Novum (Ireland)        

Irish wiring is like a hybrid of UK fittings and more like continental European wiring practices. We usually use a lot of 16 and 20amp radial circuits. Rings are permitted but they’re way less common than in the UK.

Lighting circuits are usually 6 or 10amp.

RCDs (GFCIs) were require originally only on circuits with socket outlets in the or water heating appliances etc in the 1970s and 80s. They have expanded that to all circuits. There’s a lot of use of combined breaker / RCD units called RCBOs in modern wiring.

Unlike the UK through, most homes have at least a couple of rows or breakers, as rings aren’t used much.

Also rings aren’t allowed in kitchens / utilities. Multiple radials are required instead.

Grounding is absolutely mandatory and has been since the 1930s. You won’t find any non grounded outlets. They simply don’t exist.


Post# 1180853 , Reply# 70   5/17/2023 at 15:53 (343 days old) by marky_mark (From Liverpool. Now living in Palm Springs and Dublin)        

marky_mark's profile picture

I spotted this yesterday in Koffi, Palm Springs.  This place was built in 2008, so I don't know how this ungrounded outlet has found its way in here!  I find the cockeyed installation more objectionable than the fact that it won't accept a 3-prong plug 😂

 

Mark


  Photos...       <              >      Photo 1 of 3         View Full Size
Post# 1180864 , Reply# 71   5/17/2023 at 19:29 (343 days old) by bradfordwhite (central U.S.)        

bradfordwhite's profile picture
Maybe the place was remodeled in '08 and made larger with the core of the original (most likely 60's built) structure still under the gussied up make-over.

Post# 1180894 , Reply# 72   5/18/2023 at 06:56 (342 days old) by combo52 (50 Year Repair Tech Beltsville,Md)        
Ungrounded outlet in a commercial building

combo52's profile picture
It looks like some hack put that in, that would never have been legal since the mid-50s in a commercial building.

John


Post# 1180900 , Reply# 73   5/18/2023 at 10:43 (342 days old) by chetlaham (United States)        

chetlaham's profile picture

Now thats way cool! cool

 

 

However I'd have to agree with the last two replies, that is either a hack job or the building is 70+ years old.


Post# 1180918 , Reply# 74   5/18/2023 at 19:12 (342 days old) by bradfordwhite (central U.S.)        

bradfordwhite's profile picture
According to historic images there was nothing on that site before this was built in 2008.

Post# 1182093 , Reply# 75   6/8/2023 at 18:28 (321 days old) by chetlaham (United States)        
Swiss Plug

chetlaham's profile picture

Came across these on Amazon. I'd really like the look of these in a US home.

 

 

The socket:

 

 

 

 

The plug:

 

 

 

 

 

 

 

And maybe even the wire, but in solid copper:

 

 

 

 

 

One can dream. Then again I could just buy and try lol. But I have to limit myself here, again, lol.

 

The nice thing about the swiss plug is that you can't touch the pins while energized and neither can something like a coin. The plug is small and compact, easy to insert and remove. 


Post# 1182126 , Reply# 76   6/9/2023 at 02:09 (320 days old) by donprohel (I live in Munich - Germany, but I am Italian)        
Not sure...

The socket looks Swiss (Type J: three prongs, polarised) but it might even be the Brasilian/International and proposed European (Type N).

The plug looks rather Italian (Type L, two prongs, not polarised) than the Europlug (Type C, two prongs non polarised).

However, the Italian plug and the Swiss socket are compatible in the sense that the plug is accepted by the socket


Post# 1182128 , Reply# 77   6/9/2023 at 04:26 (320 days old) by chetlaham (United States)        

chetlaham's profile picture

Good eyes!

 

Maybe its just me, but now that I look at it the top holes seem bigger than the bottom holes which would indicate a dual 10/20 amp Inmetro socket. I think its silly though, just stick with a 16 amp type N. That would be ideal.

 

 

The plug is probably Italian, ungrounded type Cs usually have the skirt around them. 

 

 

 

 

 

 

 


Post# 1182130 , Reply# 78   6/9/2023 at 04:48 (320 days old) by donprohel (I live in Munich - Germany, but I am Italian)        
Have you said "good eyes", chetlaham?

It's not only you: to me too the holes of the top socket look bigger than those of the bottom socket, but I don't have an explanation for that although looking on Wikipedia it seems that the Swiss socket may have smaller holes than the Brazilian/International proposed European socket

Post# 1182131 , Reply# 79   6/9/2023 at 05:04 (320 days old) by chetlaham (United States)        

chetlaham's profile picture

Inmetro sockets come in two ratings- 10 amp and 20 amp. The 10 amp has smaller holes that the 20 amp:

 

 

https://www.projetoderedes.com.br/artigos/imagens/Image110.gif

 

 

See 3/6 and 4/7 figures and notes: https://www.plugsocketmuseum.nl/IEC60906-1.html

 

 

My guess is the seller is trying to cover both plug sizes in one device. Such practicality would definitely get it listed on Amazon.

 

 

 


Post# 1182168 , Reply# 80   6/9/2023 at 18:11 (320 days old) by chetlaham (United States)        
My Second Favorite Plug

chetlaham's profile picture

Is the version of the NEMA 1-15 without the holes and slightly beefier solid blades. Typically reserved for 220-240 volts and used in China, Thailand and other Asian countries.

 

 

 

https://m.media-amazon.com/images/I/51-IYWSijLL._AC_SL1001_.jpg

 

 

Because Asian countries end up with Euro plug appliances from Europe and NEMA 1-15 imitations from China, outlets both grounding and non grounding are designed to take the Type A and C plug and can technically take others like the type F even though type F will be left without its earth connection.

 

 

 

 

 

 

 

 

 

Thailand takes it a step further and has their own plug type "O" plug which is a hybrid of the US NEMA 5-15 but the the round pins and spacing of the Euro plug.

 

 

https://www.liandung.com.tw/upload_files/thailand/_small_/LT-420.jpg

 

 

Lots of fun to be had!


Post# 1182177 , Reply# 81   6/9/2023 at 21:15 (319 days old) by Davey7 (Chicago)        
Since we're talking about European plugs

And sockets, outlets and receptacles, why not go whole hog and talk about wiring and panel boards (bane of my existence right now - insurance industry is forcing replacement of fuses with circuit breakers in a lot of multi-family buildings - that and plumbing fun).

So lets look at Europe, shall we, from a British perspective?














Post# 1182187 , Reply# 82   6/9/2023 at 22:39 (319 days old) by chetlaham (United States)        
Perfect Compliment to Plugs and Sockets

chetlaham's profile picture

I could write several dissertations on various EU practices; and IEC vs NEC practices. Fascinating stuff that is truly a world all on to its own. 

 

You've got the whole earthing system debate - TN-C-S vs TN-S vs TT vs IT vs PME...

 

230/400Y vs 3 x 230 sans neutral vs split phase.

 

Protecting the neutral via 2 or 4 pole MCB vs straight to the neutral bar. 

 

Radial vs ring wiring

 

Conduit vs twin and earth

 

Switches vs relays

 

Sockets vs hard wiring appliances

 

ect

 

Lots of those differences are covered in your vids. Thank you for posting them. 

 

 

 

 

 


Post# 1182196 , Reply# 83   6/10/2023 at 01:00 (319 days old) by bradfordwhite (central U.S.)        

bradfordwhite's profile picture
Obviously, the time will come when converting to a universal world standard will arrive. It will make things much easier all around. Just as there was once different standards here in the U.S. and in Britain and things were made universal per country.

I wonder what will be settled on.

I hope it's a new standard of lower voltage because many appliances now are made with power adapters to step down the power.


Post# 1193355 , Reply# 84   11/10/2023 at 20:26 by Novum (Ireland)        

It’s very unlikely tbh.

They are effectively two universal standards:

230V 50Hz - originating in European electrical systems

120V 60Hz - originating in the U.S.

There a dew odd outlier, notably Japan 100V 50Hz and 60Hz, but most of the world fits into option 1 or 2.

Plugs and sockets in 230V systems aren’t universally harmonised, but CEE 7 (the continental European ‘Schuko’ and French system) is probably the most widespread.

The Chinese type which is also basically compatible with Australia/NZ is probably the second most common type.

The U.K. type used here with 3 rectangular pins and a fused plug.

Probably the old U.K. round pin type used in India and then a raft of 2 pin designs that are semi compatible with CEE 7.

It’s unlikely they’ll ever be fully harmonised as the cost and inconvenience would outweigh any advantage at this point.


Post# 1193372 , Reply# 85   11/11/2023 at 05:23 by mrboilwash (Munich,Germany)        

mrboilwash's profile picture
"Thailand takes it a step further and has their own plug type "O" plug which is a hybrid of the US NEMA 5-15 but the the round pins and spacing of the Euro plug"

Apparently they`ve come a long way since I`ve been there 25 years ago. I remember those hybrid outlets but haven`t seen one with an earth connection.
As for plugs they seemed to have a strong preference for the American type.
No plug at all, just the wires inserted was a common sight too.
Have also seen a vacuum cleaner connected without a plug in a hotel in Italy but only once and I was still a child so it`s a long time ago.

On a side note I`ve always had a fascination for foreign plugs, outlets and light switches too. I must have been the only child in the world who noticed when an American movie had a scene in let`s say in a room in Paris and you still saw American light switches.


Post# 1193373 , Reply# 86   11/11/2023 at 05:50 by Adam-aussie-vac (Canberra ACT)        
Reply 80

You haven’t heard about the joys of finding an Australian style socket in multiple different countries that somehow have the exact same pin spacing requirements and are compatible, in the photos below, these plugs all fit Australian standards, even though they’re made across a wide variety of countries and times, even the vintage Soviet ones, one of them is actually on my vintage 220v Soviet room heater, and yes I did get the flex replaced and everything looked at and bring up to Australian standards, the only thing that it’s missing is a tilt switch, that I’ll probably ask them to see if it’s possible to retrofit, then it will officially be Soviet built Australian standards, anyway I’m getting off tangent here and the last photo is of my vintage porcelain dual voltage socket

  Photos...       <              >      Photo 1 of 7         View Full Size
Post# 1194799 , Reply# 87   12/5/2023 at 20:19 by Novum (Ireland)        

Ireland has a slightly odd history on this. We are probably the only country in Europe to have moved away from ‘Schuko’ the 16 amp plug/socket system, with the sliding ground contacts that’s used in most of Europe.

When we began standardising things in the 1920s there was no real international consensus on anything. Meanwhile the U.K. had a bit of a messy system involving multiple different round pin plugs, both two and 3 pins, all of which were mutually incompatible, as well as various non-standard systems linked to specific manufacturers. There was also no harmonised voltage in the UK at that point, which regional differences between power companies / power boards.

Ireland’s power company therefore adopted 220V 50Hz and Schuko as it had emerged as a fairly cohesive standard being used in a lot of Northern Europe and was marketed by Siemens.

It remained the preferred standard, although various U.K. round pin plugs were also used particularly during and after WWII, but domestically manufactured Schuko was common.

After WWII the UK launched by the current BS1363 and rectangular pin, fused plugs and they were designed with safety features like mandatory shutters, no ambiguity about earthing or polarity and were flush to the wall, which is whereas Schuko required much deeper boxes or was not flush.

That system was also deliberately designed to not be backward compatible with any other known system, thus would force people to upgrade to a new standard and ‘round pin’ became synonymous with obsolete / old fashioned. It also meant that there was no issue with for example grounded plugs being connected without ground.

Those arguments also all applied in Ireland, so we adopted the U.K. system officially and it would go on to completely replace any previous standards, and did so very rapidly.

If we look at it from 2023, it seems daft to have adopted an oddball standard, that was out of line with Europe, but at that time people didn’t have mobile phone chargers, laptop, and you were fairly unlikely to take a vacuum cleaner or the electric kettle on your holidays to France…

The single market was also decades away, so it just didn’t feature in the decision making logic.


Post# 1194807 , Reply# 88   12/6/2023 at 01:05 by DaveAMKrayoGuy (Oak Park, MI)        

daveamkrayoguy's profile picture
Judging from the way some of these foreign voltages outlets and whatever plugs look like, I should think or not be surprised in terms of what our US voltage is like, I suppose the US might change its entire system (soerta like going metric) to one of these designs, Canada and Mexico and other territories for that matter...

My own toys that were battery powered, if I wanted to make my own cords from string and plug-prongs made with toothpicks greatly resembled them, and my own cardboard outlets with two long vertical slots could have just had two holed dots anticipating this would be but possibly oncoming trend...



-- Dave


Post# 1194809 , Reply# 89   12/6/2023 at 01:50 by Novum (Ireland)        

There wouldn’t be much logic in anywhere with an established system changing to another system. It make some sense for completely outliers, like countries using absolutely unique outlets or voltages other than 120V 60Hz or 230V 50Hz

At the end of the day, an outlet as long as it’s fairly safely designed, is just a very simple 2 or 3 contact connector. They’re not rocket science!

The issue in Europe is one of trying to ensure a single market works. That’s why there’s been harmonisation and standardisation. It would be like if I donno, let’s say 4 of the 50 US states he’s their own plugs and sockets. You can see how that would screw up an otherwise single market for electrical appliances, requiring special versions for day Texas, Michigan, California and Hawaii.


Post# 1194810 , Reply# 90   12/6/2023 at 01:55 by petek (Ontari ari ari O )        

petek's profile picture
I remember visiting my relatives in the UK in 1967 and electric appliances didn't come with a plug on the end of the cord. You had to buy that separately to match your outlets and wire it on yourself.

Post# 1194811 , Reply# 91   12/6/2023 at 02:24 by Novum (Ireland)        

Shockingly, that only came into force in UK in 1994!

There was a slightly ridiculous notion that people needed the flexibility to fit different plugs, despite the plethora of different plugs and sockets in the U.K. having had been standardised by the 1970s.

In other EU countries it was extremely rare or illegal to supply products without plugs and probably would have been the case since the 1950s

In the Republic of Ireland it often was the case that items shipped with Europlugs / Schuko that didn’t fit the sockets and had to be cut off and replaced.

Our supply chains became more aligned with the U.K. after the EU single market came into force in 1993 but they’re back out of synch now again due to Brexit…


Post# 1194815 , Reply# 92   12/6/2023 at 05:05 by chetlaham (United States)        
Lower Voltage

chetlaham's profile picture

120 volts is already to low, going lower would present more cons than pros. People forget that because we're clinging to an obsolete voltage we've got millions of transformers wasting energy throughout buildings and millions more on utility poles spending most of their time at less than 5% load.

 

416Y/240 would consolidate 600Y/347, 480Y/277, 208Y/120, 240Δ/120 and split phase 240/120 into a single system. 416 volts for heat strips, 3 phase motors, commercial cooking equipment, high bay lighting and roadway fixtures with 240 volts for all other equipment and homes.

 

Since doubling the voltage for the same current means you can go twice the distance for the same % voltage drop or 4 times the distance at double the voltage with half the current for the same % voltage drop not even factoring the advantage of 3 phase over split phase; a single pole mount or pad mounted transformer can serve many more customers while being in the desired voltage drop bandwidth. Serving more customers means greater loading diversity with a utility transformer being subjected to a relatively flat load curve vs one with sharp peaks and troughs as in the modern US distribution system. For example, as people wake up homes begin pulling more power that begins to sharply drop as people leave for work, as people arrive for work load picks up in offices. As people head out for lunch load drops somewhat in factories and offices as load picks up in restaurants serving the lunch rush hour. Load drops at these places and pickups at work. As people leave work, load drops off  at work but increases at homes as people make dinner, turn up the heat, ect. Defrost of food market refrigerators and freezers can take place at night. The combined 24 hour load of a community resembles a valley. Transformers are most efficient when driven continuously at around 80% load.  In stark contrast all the 10, 15, 25 and 50kva transformers serving homes that see about a few amps most hours of the day with 200-300% 90 minute overloads in the morning and evenings.

 

In Europe it is common for a single 3 phase transformer to serve an entire village or at least large chunks of it- many homes, restaurants, businesses, schools, institutions, government, pump houses, ect making for a very efficient distribution system.  

 

Lower voltages waste energy, take obscene amounts of resources, create unnecessary complexity, and are way less safe.


Post# 1194816 , Reply# 93   12/6/2023 at 05:08 by chetlaham (United States)        
Rocket science

chetlaham's profile picture

Ah, but they are not far off! Consider all the safety mechanisms UK plugs and sockets have that others don't. tongue-out Plugs are an art as much as they are a science. 


Post# 1194826 , Reply# 94   12/6/2023 at 09:25 by me (Essex, UK)        
UK: When appliances came without plugs fitted.

There used to be a public safety information film regularly shown in the daytime and weekend ad breaks warning of the hazard of not fitting a plug:-








It used to annoy me when they used to supply appliances without a plug in the UK, that the flex would invariably come pre-stripped with either crimped or soldered ends for plug terminals, but would always have the outer sheath cut back far too much. If you wanted to fit the plug properly you'd have to cut and strip the wires to length loosing the crimps, although most people would just stuff the extra wire in the plug, usually resulting in the flex sheath pulling out of the cable grip.



Post# 1194827 , Reply# 95   12/6/2023 at 09:39 by foraloysius (Leeuwarden, Friesland, the Netherlands)        

foraloysius's profile picture
I noticed there are some adapter plugs that go over a Euro or Schuko plug. No need to replace the plug then.

  Photos...       <              >      Photo 1 of 2         View Full Size
Post# 1194843 , Reply# 96   12/6/2023 at 11:50 by Novum (Ireland)        

Yeah, those are used from time to time, more so with the 2.5amp Europlug variety.

They're EXTREMELY bulky with the full grounded Schuko version.
Although I have actually seen Fisher and Paykel fridges fitted with them here!

See what I mean : www.powerconnections.co.u...


Post# 1194850 , Reply# 97   12/6/2023 at 13:08 by 48bencix (Sacramento CA)        
Just wanted to add

I will put in a vote for the USA system. My home was built in 1946 and has mostly ungrounded outlets. Most of the items plugged in are ungrounded also, such as lamps in each room. Clock radio, stuff like that. There are grounded outlets in the laundry area, and kitchen. I added a couple of grounded outlets in two bedrooms to accommodate computers which had grounded outlets. The grounded outlets in the laundry and kitchen are used for higher draw appliances like microwave and the grounds are needed. I also have GFCI outlets, grounded in the two bathrooms. I do not intend to provide grounds to existing outlets which have no grounded appliances plugged in.

This home, like most in USA, has 240 volt service but not 3 phase. Local electrical charges $43 per month extra for 3 phase. So we already have the voltage to the home. I just seems excessive to have that higher voltage available to all rooms which mostly have just lights, although it would save copper. And I also like the simple plugs we have for the grounded or ungrounded appliances. Of course some appliances such as dryers and ranges have specialized plugs. Almost all outlet covers are the older style with the vertical lines. I sought out more of these to replace all outlet and switch cover plates. (Except GFCI) I found some ungrounded outlet replacements at thrift stores to replace some outlets that had lost the grip.


  View Full Size
Post# 1194857 , Reply# 98   12/6/2023 at 14:24 by petek (Ontari ari ari O )        

petek's profile picture
Same here Martin. Why fix it if it ain't broke. Our house being from 1958 is pretty sparse for outlets compared to a new build and they all are, or were, for the most part ungrounded save for the 220's on the stove, dryer etc. but I've gone around and put GFIs in many of them where I needed a 3 prong outlet. Not missing out on anything that I can think of.

Post# 1194868 , Reply# 99   12/6/2023 at 17:07 by chetlaham (United States)        
Not missing out

chetlaham's profile picture

Well, if you've never experienced 2100-3000 watt grills, fryers, toaster ovens, hair dryers, microwaves, toasters, electric kettles, panini presses, space heaters, irons, vacuum cleaners, front load washers with heaters, insta hots, electric showers, ect I could understand the sentiment. 1500-1800 watts is simply not enough power to be thoroughly practical and has motivated a lot of the energy wasting practices in the US. 

 

I think you were referring to ungrounded outlets to which I agree in full but I just wanted to use the opportunity to encourage others to discover the joys of 240 volt living.  

 


Post# 1194879 , Reply# 100   12/6/2023 at 20:21 by petek (Ontari ari ari O )        

petek's profile picture
Just comparing many of those small appliances in the UK to N.A.. such as toasters, panini presses, microwaves,, they all output about the same wattage, some more, some less, sane as here. So there's no time savings. Perhaps for water heating in a washer etc but then most people don't boil wash their laundry and never will is the true reality of life. Unless I'm missing something?

Post# 1194880 , Reply# 101   12/6/2023 at 20:34 by combo52 (50 Year Repair Tech Beltsville,Md)        
Having less power available

combo52's profile picture
Encourages energy conservation and conversely, having more power available, includes wasteful practices.

In the UK and other parts of Europe, there were crazy 3000 W vacuum cleaner sold that eventually had to be rained in with government regulation you don’t need 3000 W of power to run a vacuum cleaner.

The 3000 W tea kettles also caused power outages at times they use so much power again not necessary.

In the US when air conditioner manufactures made 240 V units they were usually much less efficient than the 120 V units because they had the power and there was no incentive to conserve with higher quality compressors and fan motors, etc. thankfully 240 V window air conditioners have all but disappeared because of efficiency gains you can easily get a 12 to 15,000 BTU air conditioner that plugs in an ordinary outlet now.

We now have the US available a full-size washer dryer combination that will run on a 15 amp 14 gauge circuit a machine large enough to do the laundry needs of any normal family and yes, it even has a water heater to boost water temperatures if needed.

I can foresee in the future to save copper that new homes may start having 10 amp circuits with 16 gauge wire for lighting circuits etc. since lighting uses so little power now in the average home.

John



Post# 1194889 , Reply# 102   12/6/2023 at 21:54 by chetlaham (United States)        

chetlaham's profile picture

Until you factor in heating cold water locally is much more efficient than idling a 50 gallon tank 24/7 or even a tank-less heater. At 120 volts it takes too long to heat cold water so you essentially have to do a hot fill. And because water cools in between runs things like DWs had to do several 2+ gallons prewashes to get the temperature hot enough for the wash before thermal holds. Front loads end up with lukewarm hot fills since the energy in the pipes simply dissipates in the walls and floors.

 

 

3000 watt appliances heat and cook faster, a big plus while using the same amount of energy. To raise 1 cup of water 100*F requires the same amount of energy regardless if the heater is 500 watts, 1,500 watts or 3000 watts.

 

But again, factor in the watts loss of the US distribution system and its clear were trying to heat the outdoors.

 

 

The code is trying to get 16 AWG copper and 10 amp circuits legal yes, however in any case 240 volts will always maximize the amount of copper used and reduce losses. There is also the addition of safety in that doubling the voltage doubles the current through a fault speeding up clearing time of fuses and circuit breakers. Earth/ground fault loop impedance of a circuit greatly improves at 230 volts to ground with any given length.  

 

 


Post# 1194904 , Reply# 103   12/7/2023 at 08:26 by me (Essex, UK)        
High wattage appliances

3,000 watt rapid boil electric kettles are common place here in the UK, I wouldn't go back to the old fashioned 2,200 watt ones we used to have, it would take too long to make tea!

Power outages in the UK are rare in the extreme, the national grid takes care of peak demands, although I gather due to underinvestment in recent years they have come very close on a few occasions to not being able to meet demand. Last outage we had must have been over a decade ago, I was told by a neighbour that the neighbourhood's transformer had "blown up", so a very exceptional circumstance.

My washing machine's element on its own is 1,950 watt, a ~2,000 watt element is pretty standard for a washing machine.

I've got a pre-ban 1,800 watt Samsung cylinder vacuum, it was rated at 350 air watts, its quicker and sucks more dust out of the carpets than any other vacuum I've owned, admittedly, I only use it on full power while using the turbo brush, or if the filter is nearly blocked.

The European Union banned high power vacuums, the problem was manufacturers were marketing their vacuums on ever bigger motor power, some as much as 2,200 watts, some people had argued that they should have been putting a performance rating like airwatts on the energy labels to address that. I can recall looking at a vacuum that was over 2,000 watts, but was such a poor design that it was only rated at something like 200 airwatts, which was no better than some 800 watt vacuums could do, meanwhile some of the more efficient 2,000 watt machines could manage 400 airwatts. We are now limited to a max of 900watt, unless it has a bypass motor (wet and dry), or an extra wide wand head (commercial vacuums).



Post# 1194911 , Reply# 104   12/7/2023 at 11:07 by Novum (Ireland)        

3kW electric kettles absolutely do not cause power outages. They’re extremely common appliances here, as are irons up to 3kW, you’ll also commonly find fan heaters, convection heaters and portable oil radiators that can go up to 3kW


1970s Argos catalogue featured plenty of them wearethemutants.com/2017/08/01/a...

Power outages are extremely rare. I’ve only ever experienced one due to a neighbour’s tree coming down in a storm and taking out the overhead drop into their house and tripping the line also feeding my house underground.

Whole thing was back online about 3 hours later thought.

Kettles compared - bear in mind the average person here (and in the UK) consumes multiple cups of tea per day:





In terms of energy consumption, they're both basically the same - one just runs for twice as long at half the wattage.




This post was last edited 12/07/2023 at 11:30
Post# 1194923 , Reply# 105   12/7/2023 at 16:57 by combo52 (50 Year Repair Tech Beltsville,Md)        
Electric tea, kettle, Speed, etc.

combo52's profile picture
Hi Jack thanks for the video

I know it uses the same amount of energy to use either a 1500 or 3000 W tea kettle, but it has been widely reported that when soap operas and other dramas on television have been played in the UK and a tense moment arrives and they go to a commercial break there have been power brownouts and blackouts, because so many people went and put on the kettle at the same time.

There certainly are a few places where higher wattage being available would be helpful such as an outdoor electric grill the ones we have here in the states are kind of weak and only 15 1600 W. Next.

There certainly are a few places where higher wattage being available would be helpful such as an outdoor electric grill the ones we have here in the states are kind of weak and only 1600 W.

But it definitely encourages energy conservation if you have to do more with less and of course, there’s an increased danger of electrical fire when you have that much power available outlets all over the house.


Post# 1194927 , Reply# 106   12/7/2023 at 18:37 by chetlaham (United States)        
Increased danger of fire

chetlaham's profile picture
Not really. Data shows Europe and the UK to have fewer electrical fires than North America at best, at worse roughly the same amount.

Fires are usually caused by joule heating (amps through a resistive connection). Good engineering assures either prevention or detection of such an event.


Post# 1194951 , Reply# 107   12/8/2023 at 00:18 by Maytag85 (Sean A806)        
Reply #94

maytag85's profile picture
Pretty munch all appliances sold here in the US since the beginning of time came to a plug and a cord. Only appliances I can think of that need to have a cord installed are dryers and electric stoves depending if it’s setup to be hardwired in or not. Wouldn’t be UL approved to sell appliances where you have to install a plug on the end of the cord.

I agree with John in reply #101, there’s no need to have 3000w vacuum cleaners and frankly, that’s overkill. Get by perfectly fine with my vintage Kirby’s that use less than 500 watts of power in use.

Not to mention, 240v is a bit more dangerous since it can carry more current which is lethal. Split phase 240v is safer since there’s no 240v potential anywhere and things like dryers here in the US/North America are backwards compatible for anyone who doesn’t have 240 available.


Post# 1194960 , Reply# 108   12/8/2023 at 06:14 by me (Essex, UK)        

I think the arguments against fitting moulded plugs were basically added cost and added packaging needed to prevent the pins of bulky uk plugs damaging the appliance. The only appliances that used to come with a plug were things like shavers and electric toothbrushes which use the much more compact uk 2 pin shaver plugs.

It was crazy that it took so long for pre-fitted plugs to be mandated, it used to result in lots of badly wire plugs and people not fitting a fuse of the correct rating. Also meant a frustrating delay wiring up the plug before you could try your brand new appliance out.

The only people who benefitted were the electrical retailers who would try to sell you an overpriced plug and pack of fuses with your purchase.



Post# 1194961 , Reply# 109   12/8/2023 at 06:42 by me (Essex, UK)        
Brown outs and blackouts

Brown outs never happen in the UK, and as far as I know, there hasn't been a blackout other than localised faults since the 1970s, and that was caused by industrial action by the miners. The national grid has computer modelling to predict demand such as ad breaks and can quickly bring on hydroelectric power from Scotland and Wales while the gas turbine stations and other generators ramp up their output. There were concerns that there could be rolling blackouts last winter due to gas shortages, and that's still a possibility this winter.

www.independent.co.uk/new...



Post# 1194962 , Reply# 110   12/8/2023 at 07:02 by foraloysius (Leeuwarden, Friesland, the Netherlands)        

foraloysius's profile picture
Well, the energy market has become more stable, Europe is less dependent on Russia. Prices have gone down too. Therefore the risk of a blackout is much smaller than last year.

Post# 1194977 , Reply# 111   12/8/2023 at 12:46 by Novum (Ireland)        
TV Pick Up -

There are surges in depend that coincide with the TV schedule, particularly Coronation Street apparently, but they are blips on a graph, not brownouts. There was a lot of tabloid nonsense about them, but there's no issue with brownouts in the UK or here, rather it just means that the UK National Grid and Eirgrid here will notice 'blips' in demand as certain ad breaks happen. 

 

It's likely less of an issue now as people tend to watch IPTV based catch up services and on demand more and may be watching soaps out of sync with real time.

 

https://en.wikipedia.org/wiki/TV_pickup

 

You used to get similar issues with radio phone-in competitions to the point that they could crash telephone exchanges, especially in the 1970s and 80s when crossbar and stepping switches were still in use. But, even early digital exchanges had issues.

 

I know for example here in Ireland, competition lines likely to generate 'bursty call' patterns all start with a particularly number.

 

1800 71 XXXX

0818 71 XXXX

 

The '71' told the digital switch or mobile network to dump the call without even attempting it, if it's under extreme pressure basically to avoid disruption. They were used with mostly telephone competitions and radio phone ins.

 

I don't think those kinds of competitions are even a thing anymore


Post# 1194988 , Reply# 112   12/8/2023 at 16:14 by me (Essex, UK)        
110 Volts in UK

110 volts is used in the UK on building sites for greater safety since tools are bound to get wet, and cables damaged.

Site transformers have an earthed centre tap on the secondary, so if they receive a shock, the voltage to ground is limited to 55 volts, and there are different sized plugs for 16 and 32 amps. You can get 110v tools that are the same wattage as their 240v equivalents.


Post# 1195132 , Reply# 113   12/10/2023 at 11:12 by Novum (Ireland)        

They’re used here in Ireland too. Different to US power tools though. it’s specifically 110V 50Hz, split phase at 180° with no neutral, from a centre tapped transformer, giving you roughly 55V to ground. It’s basically like a U.S. 240V supply, at half the voltage.

Also the plugs used are the yellow version of “CEEform” CEE 17 or BS4343, which was adopted by the IEC internationally as IEC60309 often called “Commando” or “CEEform”

RCD protected 230V(blue plugs and cables) and 400V (ref plugs and cables) are allowed on site, but not for handheld equipment.

These are plugs that are used on all industrial equipment in Europe (including the U.K.) and replaced a load of old industrial connectors of various designs both national standards and proprietary systems.

They’re heavy duty, sleeve-pin plugs with keying to avoid connections to wrong supply voltage, designed for very rough use and are latching, available in various IP ratings and can be used as couplers etc etc

Before the 1960s these used to use BS196 which was an old British industrial connector of a sleeve and pin design, but was metal clad with a scraping ground. They’re long since phased out and banned.



Forum Index:       Other Forums:                      



Comes to the Rescue!

The Discuss-o-Mat has stopped, buzzer is sounding!!!
If you would like to reply to this thread please log-in...

Discuss-O-MAT Log-In



New Members
Click Here To Sign Up.



                     


automaticwasher.org home
Discuss-o-Mat Forums
Vintage Brochures, Service and Owners Manuals
Fun Vintage Washer Ephemera
See It Wash!
Video Downloads
Audio Downloads
Picture of the Day
Patent of the Day
Photos of our Collections
The Old Aberdeen Farm
Vintage Service Manuals
Vintage washer/dryer/dishwasher to sell?
Technical/service questions?
Looking for Parts?
Website related questions?
Digital Millennium Copyright Act Policy
Our Privacy Policy