Thread Number: 93081
/ Tag: Other Home Products or Autos
Ungrounded Outlets |
[Down to Last] |
Post# 1177080   4/4/2023 at 05:03 (386 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
I'm curious if anyone still has these in their home. How do you feel about them? Do you ever find them incompatible with a random plug? Do you have any pictures that you can share?
I personally have an embarrassing soft spot for the nostalgic look, however, that is no excuse to skip on safety. Its interesting to think though, if everything was double insulated these might still be around in many newer homes today.
View Full Size
|
|
Post# 1177087 , Reply# 1   4/4/2023 at 08:57 (386 days old) by pulltostart (Mobile, AL)   |   | |
Checkrate/Likes
 
1    
Most of the houses that I've owned have been built about 1957, and typically do not have grounded branch circuits. When I've painted and worked on the houses, I've always installed new 2-prong outlets in the old wiring. In cases where newer wiring has been installed for additional circuits and they include a ground wire, I install the grounded outlets. The current house was built in 1976 and all branch circuits are grounded, which is nice; however, there is a fair amount of aluminum wiring in the house so I have to be sure how the device is wired before I buy a new outlet or switch.
I have been told previously that it's illegal to replace an ungrounded device with a grounded one if the wiring doesn't include a ground wire. This would probably be applicable when the house is sold and if the buyer is misled into thinking the house has 3-wire service throughout, only to find out later that that isn't the case.
lawrence |
Post# 1177111 , Reply# 2   4/4/2023 at 11:39 (386 days old) by JoeEkaitis (Rialto, California, USA)   |   | |
Checkrate/Likes
 
     
The only grounded outlet was the 220V in the garage for the dryer. The house was probably refitted to bring the outlets up to code after my parents passed away and we sold it. It's a Levittown-inspired rancher (single story).
The house Cathy and I live in always had 3-prong outlets. We added a 220V in the kitchen when we went from a gas stove to induction. Both are in Rialto, CA.
|
Post# 1177114 , Reply# 3   4/4/2023 at 11:43 (386 days old) by qsd-dan (West)   |   | |
Checkrate/Likes
 
5    
|
Post# 1177122 , Reply# 4   4/4/2023 at 11:58 (386 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
3    
You can replace an ungrounded with receptacle with a grounding one provided that you protect the circuit with a GFCIs and install those stickers that come with the box saying "GFCI protected" / "no equipment ground".
Joe, I'm curious as well, was the receptacle three prong or four prong? Some parts of the world like the Philippines still install ungrounded receptacles in residential. |
Post# 1177124 , Reply# 5   4/4/2023 at 12:04 (386 days old) by Marky_mark (From Liverpool. Now living in Palm Springs and Dublin)   |   | |
Checkrate/Likes
 
3    
A 240-Volt electric dryer outlet in the US is always grounded, otherwise the dryer wouldn't work.
They used to have a shared neutral-ground wire and used a 3-prong plug. This wire is required, otherwise the motor, timer, lights etc., wouldn't work as they need 120 V. The frame of the appliance is supposed to be connected to this neutral-ground wire.
Since about 1998 they have used a 4-prong plug with a separate neutral and ground. |
Post# 1177135 , Reply# 6   4/4/2023 at 13:17 (386 days old) by qsd-dan (West)   |   | |
Checkrate/Likes
 
     
A 240-Volt electric dryer outlet in the US is always grounded, otherwise the dryer wouldn't work.
In a 3 prong 240V design, everything is copasetic until a situation like a motor becomes "unbalanced" through use and more current flows through one hot prong than the other. The difference between the 2 flows through neutral becomes a live wire. Since both the neutral and ground wire are connected to the dryer cabinet, the surface of the dryer is now conducting electricity. It's a pretty rare occurrence but evidently happened enough in the past to mandate a 4 prong design in 1996. |
Post# 1177136 , Reply# 7   4/4/2023 at 13:17 (386 days old) by cfz2882 (Belle Fourche,SD)   |   | |
Checkrate/Likes
 
     
My 1952 house has a few of those outlets still.Breaker box was upgraded in 1980 when some extra circuits were added. |
Post# 1177139 , Reply# 8   4/4/2023 at 13:33 (386 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
Correct, the outlet has a grounded conductor but not a grounding conductor. Its a technicality which results in NEMA 10-30 and NEMA 10-50 receptacles being classified as "none grounding" types. 3 pole, 3 wire:
i.pinimg.com/originals/11/80/d5/...
https://www.ebay.com/itm/363342688746QUE...
Where as 6-30r and 6-50r are grounding types despite not having a neutral (2 pole 3wire). Modern NEMA 14-30r and NEMA 14-50r with a neutral and ground (3 pole 4 wire) classified as grounding types.
Code makes a distinction between a grounding and grounded conductors even though in that past it was an inadvertently common error to treat them interchangeably. Ie, you could ground a dryer through a neutral wire but you could not use the bare grounding wire in NM-B cable as the neutral.
|
Post# 1177143 , Reply# 9   4/4/2023 at 13:49 (386 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
1    
Yup! That was the big reason. Normally the the motor on a clothes dryer pulls roughly 5 amps.
10 gauge copper has a resistance of about 1.2 ohms per 1000 feet. So a reasonable worse case 100 foot home run would be 0.12 ohms. VD= IxR; would mean 5 amps x 0.12 ohms = 0.6 volts on the frame of the dryer relative to other grounded objects like the cement floor or the washer. Typically 0.6 volts isn't even perceivable, so no harm in connecting the neutral to the frame.
That is until the neutral breaks, becomes loose underneath a screw, poor contacts in the receptacle, ect... then the frame of the dryers rises to 120 volts... One hand on the dryer, one on the washer, damp hands lowering skin resistivity... one does not have to imagine why the practice was deemed risky in modern times.
For those over seas, here is the wiring diagram relevant to a US dryer-
3 wire:
i.stack.imgur.com/oYHa7.jpg...
4 wire:
i.stack.imgur.com/xB3g0.jpg... |
Post# 1177145 , Reply# 10   4/4/2023 at 14:26 (386 days old) by Marky_mark (From Liverpool. Now living in Palm Springs and Dublin)   |   | |
Checkrate/Likes
 
2    
True. I knew I wasn't being very accurate when I said the wire was a combined neutral-ground, as it is technically a neutral wire (grounded conductor) that is also used to ground the dryer's frame.
I think the reason it was changed is that just one single fault could cause the dryer's frame to become live, therefore able to deliver a fatal electric shock. This would happen if the neutral wire broke at some point along the circuit.
With the 4-prong design, I think you would need two simultaneous faults to cause this, i.e. first a break in the ground wire AND then another fault causing the live wire to contact the frame.
As for the ungrounded two-prong outlets of yesteryear, I think I may have seen these once or twice in older mid-century homes in Palm Springs, but even then it's only been the odd one or two. I have certainly seen them for sale at Home Depot. Yes they are kind of cool, if they are original to the house. I like that! |
Post# 1177152 , Reply# 11   4/4/2023 at 15:43 (386 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
To be fair, Under IEC / BS7671 standards the neutral conductor in the same Edison circuit if replicated outside the US would be classified as a PEN conductor, Protective Earth Neutral, and thus you would be correct in calling it a combined neutral-ground.
The NEC however requires it be treated it as a grounded conductor, that only by special exceptions given in the code, can ground the frame of the range or dryer.
In Eastern Europe it was common to have TN-C up to the sockets. You would only have two wires, Live and PEN, and the PEN conductor would land on the earth terminal and then jumper to the neutral terminal. Today this is forbidden, a hold over practice from the days of the soviet union.
You are correct, you'd need at least 2 failures, and with the recent code changes you'd need 3 failures. Code now requires most US dryers to be GFCI protected. The idea is that if you lost the equipment grounding conductor with a simultaneous insulation break down the GFCI would act as a last resort and trip.
I think, that as time goes on all circuits in the US will require some form GFCI or GFP protection regardless of voltage, wiring method, rating, or equipment installed. Equipment grounding conductors can and do become compromised in a world where newer standards of safety dictate that multiple things must go wrong first before any danger becomes present. |
Post# 1177164 , Reply# 12   4/4/2023 at 17:13 (386 days old) by SudsMaster (SF Bay Area, California)   |   | |
Checkrate/Likes
 
1    
I guess I am lucky here because this 1941 house was remodeled sometime in the 1960's or 70's. At that time one of the bedrooms (2) was converted to a family room, with a washer dryer closet, and another bedroom was added to the rear of the home, with its own bath. All the 120 outlets in the main house and other structures are three prong, grounded.
However, perhaps this was all done before four prong 240 volt plugs became the standard, because the plug for the original 240 volt dryer (which I soon replaced with a gas version), and all the rest of the 240 volt plugs, such as in the separate workshop (1,000 + sq ft) are all three prong. Never had a problem with any of those. I have seen four prong outlets and plugs at places like Home Depot, and always wondered what if anything they added. Now I know, so thanks. |
Post# 1177202 , Reply# 15   4/5/2023 at 01:16 (385 days old) by CircleW (NE Cincinnati OH area)   |   | |
Checkrate/Likes
 
     
Another thing is that all 2 prong receptacles sold today that I'm aware of are the cheap residential grade. I've not seen any specification or commercial grade receptacles that aren't the grounding type in many years. Residential grade devices have no place in a premium grade wiring system. |
Post# 1177214 , Reply# 16   4/5/2023 at 06:19 (385 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
|
Post# 1177218 , Reply# 17   4/5/2023 at 08:27 (385 days old) by DaveAMKrayoGuy (Oak Park, MI)   |   | |
Checkrate/Likes
 
     
The house I grew up in has had and still has to this day, ungrounded two-prong outlets which supposedly a three prong adapter could safely ground, in use of heavy duty appliances such as refrigerators and washers as well as supposrting electrical implements on gas dryers and gas stoves...
So far I haven't seen one outlet become replaced by anything three prong, except in the house I live in now having been built years later has three prongs, all grounded, but maybe meaning that the side of town I live in just conforms to updating to modern standards, versus my o.d neighborhood not being such except in the case of renouvations a number of homes with exception of that last remnant of being upgraded and updated to... Lastly, in terms of safety, we'd never encountered anything where such renewal was ever mandated due to any unsafe electrical mishaps--there weren't ever any... -- Dave |
Post# 1177241 , Reply# 18   4/5/2023 at 18:10 (385 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
Code only requires upgrades if a device is replaced, or more commonly if the wiring is being extended/upgraded to a significant degree. The rest is considered grandfathered, so, it can legally remain for the rest of eternity. Fuse panels and knob and tube are nowhere near as bad as people make them out to be, provided they've not been illegally tampered with.
In some ways it would be kind of cool if everything in homes were double insulated- no way anything could ever become live. Two wires at the service head, 2 pole breakers, 230 volt appliances. Here is such a main panel being made up in the Philippines:
Like Japan they us two wire romex through out the home, and 3 wire romex for the 3 way switching. I think blue and yellow would make good vibrant contrasting colors here in the states- with blue, yellow and red for the 3 wire romex.
View Full Size
|
Post# 1177246 , Reply# 19   4/5/2023 at 20:09 (385 days old) by bradfordwhite (central U.S.)   |   | |
Checkrate/Likes
 
1    
I especially like them in a baseboard and original not painted like in this photo
View Full Size
|
Post# 1177294 , Reply# 20   4/5/2023 at 23:59 (384 days old) by qsd-dan (West)   |   | |
Checkrate/Likes
 
2    
|
Post# 1177301 , Reply# 21   4/6/2023 at 05:57 (384 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
I think its 10 amps at 240 volts, 15 amps at 120 volts. This was the pre-NEMA days and the code at the time had a silly rule that some devices had to be rated less amps at higher voltages.
I wish the US had settled on 240 volts instead of 120. We'd probably have 10 amp general use circuits wired in 16 AWG copper.
I love your pic btw! :) |
Post# 1177343 , Reply# 23   4/6/2023 at 18:26 (384 days old) by WhiteWhiskers (Silicon Valley, California)   |   | |
Checkrate/Likes
 
4    
Amazon is selling a centered ungrounded outlet in ivory color for $6.49, ships and sold by Amazon:
www.amazon.com/Leviton-22... or you can buy a 10-pack in white for $20.98. Sold by a third-party but ships from Amazon: www.amazon.com/Leviton-Du... It's good to remember "the wide slot is white", meaning the neutral is the wide slot, connected to the white wire, which is the neutral, and the outlet is installed with the wide slot on the left side. The ivory outlet as pictured on Amazon is correct but the white outlet is upside down. Also, if you're going to do any electrical work, buy WIRING SIMPLIFIED. It's the greatest and only book you will ever need. CLICK HERE TO GO TO WhiteWhiskers's LINK |
Post# 1177352 , Reply# 24   4/6/2023 at 20:12 (384 days old) by SudsMaster (SF Bay Area, California)   |   | |
Checkrate/Likes
 
     
|
Post# 1177358 , Reply# 25   4/6/2023 at 20:44 (383 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
If feeling nostalgic, here is the 1956 version of Wiring Simplified:
inspectapedia.com/electric/Wirin...
|
Post# 1177371 , Reply# 26   4/6/2023 at 21:36 (383 days old) by SudsMaster (SF Bay Area, California)   |   | |
Checkrate/Likes
 
     
|
Post# 1177373 , Reply# 27   4/6/2023 at 21:52 (383 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
2    
|
Post# 1177382 , Reply# 28   4/6/2023 at 22:37 (383 days old) by kenmore70 (New York)   |   | |
Checkrate/Likes
 
     
What kind of appliance would require an outlet like this, with the horizontal slot? I thought I read some type of air conditioner plugs require an outlet like this but I have never seen them.
View Full Size
|
Post# 1177383 , Reply# 29   4/6/2023 at 23:19 (383 days old) by qsd-dan (West)   |   | |
Checkrate/Likes
 
     
|
Post# 1177405 , Reply# 32   4/7/2023 at 06:30 (383 days old) by WhiteWhiskers (Silicon Valley, California)   |   | |
Checkrate/Likes
 
     
Chetlaham, thank you for posting the link to the 1956 Wiring Simplified. My copy is the 39th edition from 1999, purchased in the electrical department of Home Depot. Even though a lot has changed from 1956, some things stay the same. Notice how the 1956 receptacle diagram uses ungrounded outlets while the 1999 diagram has the ground hole. The ground wire isn't shown though.
|
Post# 1177410 , Reply# 33   4/7/2023 at 09:30 (383 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
1    
Much indeed. As long as said appliance can handle 60Hz, which most can, even if listed for only 50Hz, can't tell the difference. Schuko plugs aren't even polarised so the fact any leg could/is live is taken into account safety wise.
I do this in my own home. I refuse 120 volts when I can avoid using it. I find the added engineering effort of bootlegging an impractical half voltage out of a system so odd/dated/absurd/risky. Extra effort and material just stepping backwards.
|
Post# 1177411 , Reply# 34   4/7/2023 at 09:54 (383 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
Being honest even the new additions of the book come across as dated, but, at the same time, as long as the graphics are revised to follow the lasted addition of NFPA-70 it suites its job well in teaching people.
There is one important thing that I want to clarify about that book and most other wiring books. When they use the term"ground" "going to ground" "traveling to the ground" or "grounded" in relation to clearing a fault they are referring to the path electricity takes back to the utility transformer and not the earth or soil itself. Very common misunderstanding. A typical ground rod comes in at 25 ohms and will not trip a breaker, where as a typical service neutral rarely exceeds 0.1 ohms. Fault current travels back to the main panel (or disconnect) via metal conduit or grounding conductors, to the grounding terminal in the enclosure, through the main bonding jumper, to the neutral bar and up through the service neutral going back to the transformer. It is one closed loop. The soil, earth or terra firma makes no difference in that regard.
View Full Size
|
Post# 1177535 , Reply# 35   4/8/2023 at 09:20 (382 days old) by polkanut (Wausau, WI )   |   | |
Checkrate/Likes
 
2    
Our house is a mixture of grounded & ungrounded. The original part of our house was built in 1925, and the addition was built around 1962. Funny thing though, the man who owned the house before us was in the electric motor repair business for over 50 years. You would've thought that he would have updated the electrical over the years, but this was not the case. In fact, we upgraded to a 100-amp service with a breaker box vs the old 60-amp service with only 4 fuses for the entire house. |
Post# 1177552 , Reply# 36   4/8/2023 at 12:26 (382 days old) by Adam-aussie-vac (Canberra ACT)   |   | |
Checkrate/Likes
 
     
Appliances and how you got your system to work Plus I do hope you have a 220 V coffee maker, if you don’t I can happily supply one |
Post# 1177673 , Reply# 41   4/9/2023 at 08:56 (381 days old) by DADoES (TX, U.S. of A.)   |   | |
Checkrate/Likes
 
     
|
Post# 1177674 , Reply# 42   4/9/2023 at 08:57 (381 days old) by Adam-aussie-vac (Canberra ACT)   |   | |
Checkrate/Likes
 
     
It’s electrically compatible with Australian stuff but that plug-in outlets up are rated for 15 A at 120 and 10 at 240 |
Post# 1177714 , Reply# 43   4/9/2023 at 20:00 (381 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
I have a few of these. This was one of several socket types I experimented with until I settled with schukos. Some models have a socket switch others do not. Some come with a parallel combo NEMA 1-15 / Euro plug.
|
Post# 1177716 , Reply# 44   4/9/2023 at 20:05 (381 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
I personally wish this was the dominant outlet in the US for many reasons, and it was supposed to be so, unfortunately someone must've traveled back in time screwing with critical events resulting in the after-thought NEMA 1-15/NEMA 5-15 we are stuck with today. |
Post# 1177719 , Reply# 45   4/9/2023 at 20:07 (381 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
The modern AUS adapter fits perfectly in Chinese and old non NEMA US versions- |
Post# 1177720 , Reply# 46   4/9/2023 at 20:12 (381 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
This is a NEMA 10-50 range receptacle rated 50 amps and considered "ungrounded" in NEMA standards .
I personally wish the NEMA 10-20, 10-30 and 10-50 were re-classified as grounding types (as has been done in some parts of the world) plus reintroduction of the old US crow foot. |
Post# 1177721 , Reply# 47   4/9/2023 at 20:24 (381 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
The Chinese are building these as grounding versions (technically incorrect by US standards) where the neutral pole is the grounding pole with a bonding strap to the yoke of the receptacle, pole Y as the hot and pole X is the second live or neutral when used in a 230/400Y system.
Very smart, and common sense. The round ground pins on other NEMA and NEMA-esque receptacles are essentially after thoughts, and do not make surface gripping contact the way flat contacts do.
https://www.amazon.com/Sintron-Straight-Receptacle-Suitability-Industrial/dp/B08HSYF96M/ref=sr_1_27?crid=L1XFT6TPREM2&keywords=nema%2B10-50&qid=1681089053&sprefix=nema%2B10-50%2Caps%2C119&sr=8-27&th=1
View Full Size
|
Post# 1177724 , Reply# 49   4/9/2023 at 21:00 (380 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
Amazon is the key. Try the US version, among others, that have on/off popups with Chinese sellers. Ebay for the old stuff.
In Japan they'll do that, where the cord has a separate ground wire and separate ground screw on the socket. Not something I approve of, but common there it seems.
View Full Size
|
Post# 1177725 , Reply# 50   4/9/2023 at 21:01 (380 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
This I came across on Amazon at a reduced price. When I saw it I had to get it.
View Full Size
|
Post# 1177819 , Reply# 51   4/10/2023 at 20:13 (380 days old) by SudsMaster (SF Bay Area, California)   |   | |
Checkrate/Likes
 
     
Technically speaking, the 10-50 and similar 240 volt receptacles are NOT fully grounded. This has been explained elsewhere in this thread (I think). For the safest ground, a separate path for the ground is needed; the 10-50 and similar outlets compromise this with the neutral wire. It's no safer (and perhaps less safe) than a 120 volt outlet with just two paths. One for hot, the other for neutral/ground.
That said, my laundry area in the main house, as well as the 240 volt outlets in the workshop, have only three prong outlets. Since I rarely use any of these (the dryer is gas), I'm in no hurry to change them to the latest and safest version. Some day!
Oh wait... there is a 240 volt air compressor in the workshop that I use whenever I need to fill tires. It also has a 3 prong plug. Oh well. |
Post# 1177822 , Reply# 52   4/10/2023 at 21:03 (379 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
Under NEMA they are classified as non grounding H-N-H.
However, my line of thinking is have everything go straight 240 volts. No internal 120 volt components. Have everything be 3 wire, H-G-H, and just reclassify the 10-XXs and 18-XXs as grounding types. Have the crow foot become dominant. Ditch all the other NEMA types.
At least in my world... |
Post# 1177824 , Reply# 53   4/10/2023 at 21:31 (379 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
1    
The US residential system is split phase, a center tapped 240 volt winding. Each home receives two hots and one grounded neutral. The system is TN-C-S or rather technically PME. Both hot legs are 180* out of phase, so between each hot and neutral (of ground) we get 120 volts, but between each hot wire we get full 240 volts.
en.wikipedia.org/wiki/Split-phas... |
Post# 1177831 , Reply# 54   4/11/2023 at 00:38 (379 days old) by CircleW (NE Cincinnati OH area)   |   | |
Checkrate/Likes
 
     
There are already grounded receptacles for equipment that operates solely at 240 volts. For example, the NEMA 6-50 is rated for 50 amps, no neutral - just the equipment ground. That said, I've seen installations that used the 10-50 for that purpose. |
Post# 1177838 , Reply# 55   4/11/2023 at 05:56 (379 days old) by ozzie908 (Lincoln UK)   |   | |
Checkrate/Likes
 
1    
May leave some people agog but they are all switched and all earthed/grounded even light fittings are grounded.
No matter what you choose to connect there is no extra wiring needed apart from Stove's and showers. All plugs are three prong too and each plug is fused for safety they may be bulky but it makes life safer and easier |
Post# 1177853 , Reply# 56   4/11/2023 at 11:33 (379 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
|
Post# 1177858 , Reply# 58   4/11/2023 at 12:48 (379 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
The wiring in the wall is already protected via MCB. The fuse protects to cord itself and also reduces the amount incident energy released at the point of short circuit, if the cord became shorted. With a 32 amp MCB the cord may melt before the MCB trips (adiabatic limit of the cord's conductor exceeded), or just arc/sputter at the point the cord is damaged, but with the fuse (in the plug) a fault in the cord instantly blows said plug fuse before anything bad can happen. The fuse responds faster, at a lower current, than the 32 amp MCB can.
Ring circuits, at least back in the day, allowed much more power to be supplied to a building level via less copper. The load diversity also helped maximize the savings as it is not likely everything would be on at once. A whole residential lower level could be fed from a single 32 amp circuit, a second 32 amp ring socket circuit for the upstairs, then one or two 6 or 10 amp radial lighting circuits. A 40 amp for the cooker, maybe another circuit for the boiler.
There has to be a ground pin on the plug even if the appliance is double insulated as the safety shutters in the plug will not open. Ingenious idea as the shutters provide both child protection and rejection of a plug missing its ground pin. In the US missing equipment ground pins on metal tools like drills made for the bulk of electrocutions.
Attached Image courtesy of "Fatally Flawed"
electrical.theiet.org/wiring-mat...
View Full Size
|
Post# 1177900 , Reply# 60   4/11/2023 at 22:24 (378 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
UK homes typically have at least one 6 or 10 amp radial lighting circuit in that should the ring MCB blow, hardwired ceiling and wall mounted fixtures are still functional.
A 32 amp ring and one 10 amp lighting circuit in the UK can supply more power than 4 120 volt circuits- two rated at 20 amps and two at 15 amps in a typical US home. Hence there are no code requirements restricting a circuit to any particular area as you find in the NEC. |
Post# 1178066 , Reply# 61   4/13/2023 at 23:27 (376 days old) by SudsMaster (SF Bay Area, California)   |   | |
Checkrate/Likes
 
     
Well, went to Home Depot and picked up my copy of "Wiring Simplified". It looks good.
If I have a complaint, though, it would be that the type is a bit small. Not so small that I need a magnifier, but sort of on the edge.
Anyway, I'm wondering if the original edition was in a larger format (2017 version or earlier, that is). Maybe not, since the added size might adversely affect sticking it in a tool box. LOL.
Anyway, I'll be roaming through Wiring Simplified over the next few days/weeks/months.
PS- About 40 years ago, I had a temp job with an electrical contractor who had helped wire a new building for the lab I was working. Wiring Simplified would have been a good read back then, too. |
Post# 1178177 , Reply# 62   4/15/2023 at 07:46 (375 days old) by combo52 (50 Year Repair Tech Beltsville,Md)   |   | |
Checkrate/Likes
 
     
|
Post# 1178233 , Reply# 63   4/15/2023 at 15:38 (375 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
|
Post# 1180186 , Reply# 64   5/9/2023 at 07:44 (351 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
1    
the white ones were sold out, but I did manage to get some brown ones- |
Post# 1180201 , Reply# 65   5/9/2023 at 12:40 (351 days old) by bradfordwhite (central U.S.)   |   | |
Checkrate/Likes
 
     
According to the book, in 1956 one could still freely install knob and tube wiring but it also says most people don't because it's too expensive. lol
These days the ideal electric system would have all lighting wired as 12 volt DC, most outlets in the bedrooms, living rooms, and offices/libraries being 12 volt DC with USB outlets. Really the only place 120 volt AC is needed is at specific appliances like the water heater, washing machine, kitchen counter, etc. and most of those appliances are located in only a few rooms. With the main wiring system being 12 DC it's easy to draw power from a solar system battery bank. All the LED lights are low voltage and need to have built in transformers to work on the current 120volt AC set up. I think I would put one 120 v AC outlet in each bedroom or living room next to the entrance at a convenient height of 30"
View Full Size
|
Post# 1180271 , Reply# 67   5/10/2023 at 12:07 (350 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
|
Post# 1180385 , Reply# 68   5/11/2023 at 21:26 (348 days old) by bradfordwhite (central U.S.)   |   | |
Checkrate/Likes
 
     
Yes with D.C. one has to be cognizant of voltage drop even from room to room but it's mainly within one's home. Most solar arrays are on the roof or near by. Having to beef up some branch main lines is a small price to pay for energy independence imo.
I suggest the 12 volt for simplicity sake. Avoiding transformers and the like which can be high maintenance, expensive to replace and points of noise, heat, and energy usage. I'd rather invest money one time in thicker gauge wires so one can move power from one point in a home to another efficiently. Copper wires don't break down. An independent 48 volt system is preferred for the few high watt use appliances where stepping up the 12 volt to 120 volt AC is preferred. Technology is always changing, becoming more affordable and easier to use. It's just incredible. |
Post# 1180853 , Reply# 70   5/17/2023 at 15:53 (343 days old) by marky_mark (From Liverpool. Now living in Palm Springs and Dublin)   |   | |
Checkrate/Likes
 
     
I spotted this yesterday in Koffi, Palm Springs. This place was built in 2008, so I don't know how this ungrounded outlet has found its way in here! I find the cockeyed installation more objectionable than the fact that it won't accept a 3-prong plug 😂
Mark |
Post# 1180864 , Reply# 71   5/17/2023 at 19:29 (343 days old) by bradfordwhite (central U.S.)   |   | |
Checkrate/Likes
 
     
|
Post# 1180894 , Reply# 72   5/18/2023 at 06:56 (342 days old) by combo52 (50 Year Repair Tech Beltsville,Md)   |   | |
Checkrate/Likes
 
     
|
Post# 1180900 , Reply# 73   5/18/2023 at 10:43 (342 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
|
Post# 1180918 , Reply# 74   5/18/2023 at 19:12 (342 days old) by bradfordwhite (central U.S.)   |   | |
Checkrate/Likes
 
1    
|
Post# 1182093 , Reply# 75   6/8/2023 at 18:28 (321 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
Came across these on Amazon. I'd really like the look of these in a US home.
The socket:
The plug:
And maybe even the wire, but in solid copper:
One can dream. Then again I could just buy and try lol. But I have to limit myself here, again, lol.
The nice thing about the swiss plug is that you can't touch the pins while energized and neither can something like a coin. The plug is small and compact, easy to insert and remove. |
Post# 1182126 , Reply# 76   6/9/2023 at 02:09 (320 days old) by donprohel (I live in Munich - Germany, but I am Italian)   |   | |
Checkrate/Likes
 
     
The socket looks Swiss (Type J: three prongs, polarised) but it might even be the Brasilian/International and proposed European (Type N). The plug looks rather Italian (Type L, two prongs, not polarised) than the Europlug (Type C, two prongs non polarised). However, the Italian plug and the Swiss socket are compatible in the sense that the plug is accepted by the socket |
Post# 1182128 , Reply# 77   6/9/2023 at 04:26 (320 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
Good eyes!
Maybe its just me, but now that I look at it the top holes seem bigger than the bottom holes which would indicate a dual 10/20 amp Inmetro socket. I think its silly though, just stick with a 16 amp type N. That would be ideal.
The plug is probably Italian, ungrounded type Cs usually have the skirt around them.
|
Post# 1182130 , Reply# 78   6/9/2023 at 04:48 (320 days old) by donprohel (I live in Munich - Germany, but I am Italian)   |   | |
Checkrate/Likes
 
     
It's not only you: to me too the holes of the top socket look bigger than those of the bottom socket, but I don't have an explanation for that although looking on Wikipedia it seems that the Swiss socket may have smaller holes than the Brazilian/International proposed European socket |
Post# 1182131 , Reply# 79   6/9/2023 at 05:04 (320 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
Inmetro sockets come in two ratings- 10 amp and 20 amp. The 10 amp has smaller holes that the 20 amp:
See 3/6 and 4/7 figures and notes: https://www.plugsocketmuseum.nl/IEC60906-1.html
My guess is the seller is trying to cover both plug sizes in one device. Such practicality would definitely get it listed on Amazon.
|
Post# 1182168 , Reply# 80   6/9/2023 at 18:11 (320 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
Is the version of the NEMA 1-15 without the holes and slightly beefier solid blades. Typically reserved for 220-240 volts and used in China, Thailand and other Asian countries.
Because Asian countries end up with Euro plug appliances from Europe and NEMA 1-15 imitations from China, outlets both grounding and non grounding are designed to take the Type A and C plug and can technically take others like the type F even though type F will be left without its earth connection.
Thailand takes it a step further and has their own plug type "O" plug which is a hybrid of the US NEMA 5-15 but the the round pins and spacing of the Euro plug.
Lots of fun to be had! |
Post# 1182187 , Reply# 82   6/9/2023 at 22:39 (319 days old) by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
I could write several dissertations on various EU practices; and IEC vs NEC practices. Fascinating stuff that is truly a world all on to its own.
You've got the whole earthing system debate - TN-C-S vs TN-S vs TT vs IT vs PME...
230/400Y vs 3 x 230 sans neutral vs split phase.
Protecting the neutral via 2 or 4 pole MCB vs straight to the neutral bar.
Radial vs ring wiring
Conduit vs twin and earth
Switches vs relays
Sockets vs hard wiring appliances
ect
Lots of those differences are covered in your vids. Thank you for posting them.
|
Post# 1182196 , Reply# 83   6/10/2023 at 01:00 (319 days old) by bradfordwhite (central U.S.)   |   | |
Checkrate/Likes
 
     
Obviously, the time will come when converting to a universal world standard will arrive. It will make things much easier all around. Just as there was once different standards here in the U.S. and in Britain and things were made universal per country.
I wonder what will be settled on. I hope it's a new standard of lower voltage because many appliances now are made with power adapters to step down the power. |
Post# 1193372 , Reply# 85   11/11/2023 at 05:23 by mrboilwash (Munich,Germany)   |   | |
Checkrate/Likes
 
1    
"Thailand takes it a step further and has their own plug type "O" plug which is a hybrid of the US NEMA 5-15 but the the round pins and spacing of the Euro plug"
Apparently they`ve come a long way since I`ve been there 25 years ago. I remember those hybrid outlets but haven`t seen one with an earth connection. As for plugs they seemed to have a strong preference for the American type. No plug at all, just the wires inserted was a common sight too. Have also seen a vacuum cleaner connected without a plug in a hotel in Italy but only once and I was still a child so it`s a long time ago. On a side note I`ve always had a fascination for foreign plugs, outlets and light switches too. I must have been the only child in the world who noticed when an American movie had a scene in let`s say in a room in Paris and you still saw American light switches. |
Post# 1194807 , Reply# 88   12/6/2023 at 01:05 by DaveAMKrayoGuy (Oak Park, MI)   |   | |
Checkrate/Likes
 
     
Judging from the way some of these foreign voltages outlets and whatever plugs look like, I should think or not be surprised in terms of what our US voltage is like, I suppose the US might change its entire system (soerta like going metric) to one of these designs, Canada and Mexico and other territories for that matter...
My own toys that were battery powered, if I wanted to make my own cords from string and plug-prongs made with toothpicks greatly resembled them, and my own cardboard outlets with two long vertical slots could have just had two holed dots anticipating this would be but possibly oncoming trend... -- Dave |
Post# 1194810 , Reply# 90   12/6/2023 at 01:55 by petek (Ontari ari ari O )   |   | |
Checkrate/Likes
 
     
|
Post# 1194815 , Reply# 92   12/6/2023 at 05:05 by chetlaham (United States)   |   | |
Checkrate/Likes
 
1    
120 volts is already to low, going lower would present more cons than pros. People forget that because we're clinging to an obsolete voltage we've got millions of transformers wasting energy throughout buildings and millions more on utility poles spending most of their time at less than 5% load.
416Y/240 would consolidate 600Y/347, 480Y/277, 208Y/120, 240Δ/120 and split phase 240/120 into a single system. 416 volts for heat strips, 3 phase motors, commercial cooking equipment, high bay lighting and roadway fixtures with 240 volts for all other equipment and homes.
Since doubling the voltage for the same current means you can go twice the distance for the same % voltage drop or 4 times the distance at double the voltage with half the current for the same % voltage drop not even factoring the advantage of 3 phase over split phase; a single pole mount or pad mounted transformer can serve many more customers while being in the desired voltage drop bandwidth. Serving more customers means greater loading diversity with a utility transformer being subjected to a relatively flat load curve vs one with sharp peaks and troughs as in the modern US distribution system. For example, as people wake up homes begin pulling more power that begins to sharply drop as people leave for work, as people arrive for work load picks up in offices. As people head out for lunch load drops somewhat in factories and offices as load picks up in restaurants serving the lunch rush hour. Load drops at these places and pickups at work. As people leave work, load drops off at work but increases at homes as people make dinner, turn up the heat, ect. Defrost of food market refrigerators and freezers can take place at night. The combined 24 hour load of a community resembles a valley. Transformers are most efficient when driven continuously at around 80% load. In stark contrast all the 10, 15, 25 and 50kva transformers serving homes that see about a few amps most hours of the day with 200-300% 90 minute overloads in the morning and evenings.
In Europe it is common for a single 3 phase transformer to serve an entire village or at least large chunks of it- many homes, restaurants, businesses, schools, institutions, government, pump houses, ect making for a very efficient distribution system.
Lower voltages waste energy, take obscene amounts of resources, create unnecessary complexity, and are way less safe. |
Post# 1194816 , Reply# 93   12/6/2023 at 05:08 by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
|
Post# 1194827 , Reply# 95   12/6/2023 at 09:39 by foraloysius (Leeuwarden, Friesland, the Netherlands)   |   | |
Checkrate/Likes
 
     
I noticed there are some adapter plugs that go over a Euro or Schuko plug. No need to replace the plug then.
|
Post# 1194857 , Reply# 98   12/6/2023 at 14:24 by petek (Ontari ari ari O )   |   | |
Checkrate/Likes
 
1    
Same here Martin. Why fix it if it ain't broke. Our house being from 1958 is pretty sparse for outlets compared to a new build and they all are, or were, for the most part ungrounded save for the 220's on the stove, dryer etc. but I've gone around and put GFIs in many of them where I needed a 3 prong outlet. Not missing out on anything that I can think of.
|
Post# 1194868 , Reply# 99   12/6/2023 at 17:07 by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
Well, if you've never experienced 2100-3000 watt grills, fryers, toaster ovens, hair dryers, microwaves, toasters, electric kettles, panini presses, space heaters, irons, vacuum cleaners, front load washers with heaters, insta hots, electric showers, ect I could understand the sentiment. 1500-1800 watts is simply not enough power to be thoroughly practical and has motivated a lot of the energy wasting practices in the US.
I think you were referring to ungrounded outlets to which I agree in full but I just wanted to use the opportunity to encourage others to discover the joys of 240 volt living.
|
Post# 1194879 , Reply# 100   12/6/2023 at 20:21 by petek (Ontari ari ari O )   |   | |
Checkrate/Likes
 
     
Just comparing many of those small appliances in the UK to N.A.. such as toasters, panini presses, microwaves,, they all output about the same wattage, some more, some less, sane as here. So there's no time savings. Perhaps for water heating in a washer etc but then most people don't boil wash their laundry and never will is the true reality of life. Unless I'm missing something?
|
Post# 1194880 , Reply# 101   12/6/2023 at 20:34 by combo52 (50 Year Repair Tech Beltsville,Md)   |   | |
Checkrate/Likes
 
1    
Encourages energy conservation and conversely, having more power available, includes wasteful practices.
In the UK and other parts of Europe, there were crazy 3000 W vacuum cleaner sold that eventually had to be rained in with government regulation you don’t need 3000 W of power to run a vacuum cleaner. The 3000 W tea kettles also caused power outages at times they use so much power again not necessary. In the US when air conditioner manufactures made 240 V units they were usually much less efficient than the 120 V units because they had the power and there was no incentive to conserve with higher quality compressors and fan motors, etc. thankfully 240 V window air conditioners have all but disappeared because of efficiency gains you can easily get a 12 to 15,000 BTU air conditioner that plugs in an ordinary outlet now. We now have the US available a full-size washer dryer combination that will run on a 15 amp 14 gauge circuit a machine large enough to do the laundry needs of any normal family and yes, it even has a water heater to boost water temperatures if needed. I can foresee in the future to save copper that new homes may start having 10 amp circuits with 16 gauge wire for lighting circuits etc. since lighting uses so little power now in the average home. John |
Post# 1194889 , Reply# 102   12/6/2023 at 21:54 by chetlaham (United States)   |   | |
Checkrate/Likes
 
1    
Until you factor in heating cold water locally is much more efficient than idling a 50 gallon tank 24/7 or even a tank-less heater. At 120 volts it takes too long to heat cold water so you essentially have to do a hot fill. And because water cools in between runs things like DWs had to do several 2+ gallons prewashes to get the temperature hot enough for the wash before thermal holds. Front loads end up with lukewarm hot fills since the energy in the pipes simply dissipates in the walls and floors.
3000 watt appliances heat and cook faster, a big plus while using the same amount of energy. To raise 1 cup of water 100*F requires the same amount of energy regardless if the heater is 500 watts, 1,500 watts or 3000 watts.
But again, factor in the watts loss of the US distribution system and its clear were trying to heat the outdoors.
The code is trying to get 16 AWG copper and 10 amp circuits legal yes, however in any case 240 volts will always maximize the amount of copper used and reduce losses. There is also the addition of safety in that doubling the voltage doubles the current through a fault speeding up clearing time of fuses and circuit breakers. Earth/ground fault loop impedance of a circuit greatly improves at 230 volts to ground with any given length.
|
Post# 1194923 , Reply# 105   12/7/2023 at 16:57 by combo52 (50 Year Repair Tech Beltsville,Md)   |   | |
Checkrate/Likes
 
     
Hi Jack thanks for the video
I know it uses the same amount of energy to use either a 1500 or 3000 W tea kettle, but it has been widely reported that when soap operas and other dramas on television have been played in the UK and a tense moment arrives and they go to a commercial break there have been power brownouts and blackouts, because so many people went and put on the kettle at the same time. There certainly are a few places where higher wattage being available would be helpful such as an outdoor electric grill the ones we have here in the states are kind of weak and only 15 1600 W. Next. There certainly are a few places where higher wattage being available would be helpful such as an outdoor electric grill the ones we have here in the states are kind of weak and only 1600 W. But it definitely encourages energy conservation if you have to do more with less and of course, there’s an increased danger of electrical fire when you have that much power available outlets all over the house. |
Post# 1194927 , Reply# 106   12/7/2023 at 18:37 by chetlaham (United States)   |   | |
Checkrate/Likes
 
     
|
Post# 1194951 , Reply# 107   12/8/2023 at 00:18 by Maytag85 (Sean A806)   |   | |
Checkrate/Likes
 
2    
Pretty munch all appliances sold here in the US since the beginning of time came to a plug and a cord. Only appliances I can think of that need to have a cord installed are dryers and electric stoves depending if it’s setup to be hardwired in or not. Wouldn’t be UL approved to sell appliances where you have to install a plug on the end of the cord.
I agree with John in reply #101, there’s no need to have 3000w vacuum cleaners and frankly, that’s overkill. Get by perfectly fine with my vintage Kirby’s that use less than 500 watts of power in use. Not to mention, 240v is a bit more dangerous since it can carry more current which is lethal. Split phase 240v is safer since there’s no 240v potential anywhere and things like dryers here in the US/North America are backwards compatible for anyone who doesn’t have 240 available. |
Post# 1194962 , Reply# 110   12/8/2023 at 07:02 by foraloysius (Leeuwarden, Friesland, the Netherlands)   |   | |
Checkrate/Likes
 
2    
|